2012-01-12 14:05:30SERVICE IS ON ZERO LOT LINE OF BUILDING.
  
 NEED SURVEY AND PERMISSION FROM OWNER OF BUILDING AND
 OWNER OF PARKING LOT
 TO HAVE SERVICE ON THAT SIDE OF BUILDING.
  
 FAULT CURRENT SUPPLIED STATES 45,159 AMPERES AT FPL
 NEED 50,000 AIC RATED FUSES/CIRCUIT BREAKER AT MAIN.
  
  
  
 J. LEAHY 01/12/12