Plan Review Notes
Plan Review Notes For Permit 12010158
Permit Number 12010158
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-26 10:20:49PERMIT # 12010158
 ADDRESS: 8020 S DIXIE HWY
 CONTRACTOR: CANO INC
 TEL: 561-543-1290
  
 2007/09 FBC-BUILDING
 2007/09 EXISTING BUILDING CODE
 LEVEL II ALTERATIONS: EXSST BLDG CODE: 701.3 ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE- BUILDING.
  
 1) SHEET A2.1 THE DETAIL F PARTIAL FOUNDATION PLAN
 INDICATES THE USE OF A 8X8 INCH THICKENED EDGE FOR THE
 FOUNDATION WHERE AS THIS IS CONSIDERED AN ADDITION WITH
 WALL LOADING PLEASE SEE NOTE ON SHEET A3.1 FOUNDATION
 NOTE 3, THE FOUNDATION SHALL BE 1?-0? BELOW EXTERIOR
 FINISH GRADE, PLEASE ALSO REVIEW FBC-B 1805.2 DEPTH OF
 FOUNDATIONS.
  
 2) SHEET A2.1 IT APPEARS THERE IS A DISCREPANCY IN THE
 PLANS WALL SECTION A SHEET A2.1 INDICATES THE USE OF
 5/8 INCH EXT GRADE PLYWOOD WHERE AS SHEET A3.1 UNDER
 THE HEADING OF NOTE 5 PLYWOOD SHEATHING SUB-HEADING A
 INDICATES THE USE OF 5/8 INCH EXTERIOR GRADE GYPSUM
 SHEATHING.
  
 3) PLEASE NOTE IF THE 5/8 INCH EXTERIOR GRADE PLYWOOD
 WILL BE INSTALLED COMPLIANCE WITH FBC-B 2304.11.2.6 IF
 LESS THAN 6 INCHES BETWEEN THE WALL SHEATHING AND GRADE
 SHEATHING, SIDING AND WOOD WALL FRAMING ARE OF
 NATURALLY DURABLE WOOD OR PRE-PRESERVATIVE-TREATED
 WOOD.
  
 4) SHEET A2.1 DETAIL G INDICATES THE USE OF A PRECAST
 CONCRETE PAD FOR CONDENSER ON ALUMINUM RACK. PLEASE
 PROVIDE PRODUCT APPROVALS FOR THE PRE-CAST CONCRETE PAD
 AND FOR THE ALUMINUM RACK, APPROVED FOR USE IN A 140
 MPH WIND ZONE. RULE 9N-03.
  
 5) SHEET A2.1 DETAIL B INDICATES THE METAL STUD BEING
 ANCHORED INTO A BUILT DOWN HEADER SYSTEM, PLEASE
 PROVIDE THE TYPE OF FASTENER TO BE INSTALLED TO ANCHOR
 THIS WALL SECTION TO THE EXISTING HEADER. INDICATE TYPE
 OF FASTENER, SPACING AND SIZE OF ANCHOR.
  
 6A) SHEET A2.1 SECTION G ALSO INDICATES A NEW EXTERIOR
 FREEZER DOOR AND THE USE OF STORM SHUTTERS FOR HIGH
 WIND EVENTS.
 RULE 9N-03 REQUIRES PRODUCT APPROVALS FOR ALL EXTERIOR
 DOORS. 9N-03 (31)(A). EVEN THOUGH STORM SHUTTERS ARE TO
 BE APPLIED THE STORM SHUTTERS ONLY PROTECT THE FREEZER
 DOOR FROM LARGE MISSILE IMPACT NOT FROM POSITIVE &
 NEGATIVE PRESSURES.
  
 6B) STORM SHUTTERS ALSO REQUIRE PRODUCT APPROVALS RULE
 9N-03(31)(E).
  
 7) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  