2012-01-26 10:20:49 | PERMIT # 12010158 |
| ADDRESS: 8020 S DIXIE HWY |
| CONTRACTOR: CANO INC |
| TEL: 561-543-1290 |
| |
| 2007/09 FBC-BUILDING |
| 2007/09 EXISTING BUILDING CODE |
| LEVEL II ALTERATIONS: EXSST BLDG CODE: 701.3 ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE- BUILDING. |
| |
| 1) SHEET A2.1 THE DETAIL F PARTIAL FOUNDATION PLAN |
| INDICATES THE USE OF A 8X8 INCH THICKENED EDGE FOR THE |
| FOUNDATION WHERE AS THIS IS CONSIDERED AN ADDITION WITH |
| WALL LOADING PLEASE SEE NOTE ON SHEET A3.1 FOUNDATION |
| NOTE 3, THE FOUNDATION SHALL BE 1?-0? BELOW EXTERIOR |
| FINISH GRADE, PLEASE ALSO REVIEW FBC-B 1805.2 DEPTH OF |
| FOUNDATIONS. |
| |
| 2) SHEET A2.1 IT APPEARS THERE IS A DISCREPANCY IN THE |
| PLANS WALL SECTION A SHEET A2.1 INDICATES THE USE OF |
| 5/8 INCH EXT GRADE PLYWOOD WHERE AS SHEET A3.1 UNDER |
| THE HEADING OF NOTE 5 PLYWOOD SHEATHING SUB-HEADING A |
| INDICATES THE USE OF 5/8 INCH EXTERIOR GRADE GYPSUM |
| SHEATHING. |
| |
| 3) PLEASE NOTE IF THE 5/8 INCH EXTERIOR GRADE PLYWOOD |
| WILL BE INSTALLED COMPLIANCE WITH FBC-B 2304.11.2.6 IF |
| LESS THAN 6 INCHES BETWEEN THE WALL SHEATHING AND GRADE |
| SHEATHING, SIDING AND WOOD WALL FRAMING ARE OF |
| NATURALLY DURABLE WOOD OR PRE-PRESERVATIVE-TREATED |
| WOOD. |
| |
| 4) SHEET A2.1 DETAIL G INDICATES THE USE OF A PRECAST |
| CONCRETE PAD FOR CONDENSER ON ALUMINUM RACK. PLEASE |
| PROVIDE PRODUCT APPROVALS FOR THE PRE-CAST CONCRETE PAD |
| AND FOR THE ALUMINUM RACK, APPROVED FOR USE IN A 140 |
| MPH WIND ZONE. RULE 9N-03. |
| |
| 5) SHEET A2.1 DETAIL B INDICATES THE METAL STUD BEING |
| ANCHORED INTO A BUILT DOWN HEADER SYSTEM, PLEASE |
| PROVIDE THE TYPE OF FASTENER TO BE INSTALLED TO ANCHOR |
| THIS WALL SECTION TO THE EXISTING HEADER. INDICATE TYPE |
| OF FASTENER, SPACING AND SIZE OF ANCHOR. |
| |
| 6A) SHEET A2.1 SECTION G ALSO INDICATES A NEW EXTERIOR |
| FREEZER DOOR AND THE USE OF STORM SHUTTERS FOR HIGH |
| WIND EVENTS. |
| RULE 9N-03 REQUIRES PRODUCT APPROVALS FOR ALL EXTERIOR |
| DOORS. 9N-03 (31)(A). EVEN THOUGH STORM SHUTTERS ARE TO |
| BE APPLIED THE STORM SHUTTERS ONLY PROTECT THE FREEZER |
| DOOR FROM LARGE MISSILE IMPACT NOT FROM POSITIVE & |
| NEGATIVE PRESSURES. |
| |
| 6B) STORM SHUTTERS ALSO REQUIRE PRODUCT APPROVALS RULE |
| 9N-03(31)(E). |
| |
| 7) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |