 PERMIT #12010135
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE FIRE LANE FOR THE BUILDING REQUIRES AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE.
  