Plan Review Notes
Plan Review Notes For Permit 12010135
Permit Number 12010135
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-27 13:48:27BUILDING PLAN REVIEW
 PERMIT: 12010135
 ADD: 4601 S FLAGLER DR
 CONT: AMERICAN AWNING
 TEL: (561)699-7648
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE FIRST QUESTION IS THE AWNING IS DEPICTED AS
 ATTACHING TO THE BUILDING AND THEN THE VERTICAL
 SUPPORTS ARE 4'-9" AWAY FROM THE BUILDING. THE SURVEY
 PROIDED DOES NOT INDICATE HOW WIDE THE SIDEWALK IS, THE
 QUESTION WOULD BE THE 2 VERTICAL LEG LOCATION IS THIS
 IN THE SIDEWALK OR LOCATED IN THE DRIVEWAY? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 2) THIS LOCATION OF THIS CANOPY INDICATES THIS TO BE A
 PLACE OF WORSHIP WHICH IS EXEMPT FROM ACCESSIBILITY
 REQUIREMENTS UNDER THIS CODE. THE PLANS DO INDICATE
 THAT THE CLEAR VERTICAL HEIGHT IS TO BE 7'-6" FROM
 GRADE, IF A DISSABLED PERSON WERE TO TRY TO USE THIS
 AWNING FOR COVERAGE WHEN RAINING THEY WOULD NOT BE ABLE
 TO DRIVE UNDERNEATH THE CANOPY(IF USING A VAN),
 PASSENGER LOADING ZONES REQUIRE A CLEAR 114 INCHES
 11-4.6.5. THIS IS JUST A POINT TO BRING UP FOR THE
 OWNERS TO BE AWARE OF. PLACES OF WORSHIP ARE EXEMPT
 FROM THE ACCESSIBILTY CODE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  