2012-03-22 11:48:41PLANS DENIED
 1) PROVIDE MORE INFORMATION ON THE EQUIPMENT SCHEDULE
 CONDENSER MODEL NUMBER AND INFORMATION ON THE
 AIR HANDLER UNIT. SECTION 301.5 FBC (M) 2007
 2) PROVIDE HEAT LOADS AND ENERGY CALCULATIONS FOR THE
 ADDITION.
 3) ON THE DETAIL FOR THE CONDENSER STAND TO ROOF WHAT
 SIZE BOLTS
 ARE USED . SECTION 301.12 WIND RESISTANCE.2007 FBC (M)
 4) PROVIDE PRODUCT APPROVALS ON THE CONDENSER STAND
 WITH THE
 PLANS SECTION 106.3.3 FBC 2007