Plan Review Notes For Permit 12010122 |
Permit Number |
12010122 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-02-29 13:34:54 | 12010122 | | 429 BELVEDERE ROAD | | RESIDENTIAL LOFT RENOVATION | | | | INDICATE SIZE OF FEEDERS TO 150 AMPERE PANELBOARD. | | IS THE ELECTRIC SERVICE EXISTING OR NEW? VERIFY THE | | ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND GROUPED IN | | ONE LOCATION. NEC 230.2, 230.71 | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. 2008 NEC 250.94 | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | UNIT ENTRANCE. NEC 210.52 | | ALL RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC | | 406.11 | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | OF EACH ROOM USED FOR SLEEPING IN HOMES WITH GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE. 2007 | | FBC R313 | | | | | | ROBERT LECKY | | ELECTRIC PLAN REVIEWER | | [email protected] | | 561-805-6718 | | |
|