Plan Review Notes
Plan Review Notes For Permit 12010122
Permit Number 12010122
Review Stop E
Sequence Number 2
Notes
Date Text
2012-02-29 13:34:5412010122
 429 BELVEDERE ROAD
 RESIDENTIAL LOFT RENOVATION
  
 INDICATE SIZE OF FEEDERS TO 150 AMPERE PANELBOARD.
 IS THE ELECTRIC SERVICE EXISTING OR NEW? VERIFY THE
 ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND GROUPED IN
 ONE LOCATION. NEC 230.2, 230.71
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 UNIT ENTRANCE. NEC 210.52
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING IN HOMES WITH GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE. 2007
 FBC R313
  
  