2012-01-17 16:08:10 | BUILDING PLAN REVIEW |
| PERMIT: 12010122 |
| ADD: 429 BELVEDERE RD |
| CONT: C & S EXPERTISE INC. |
| TEL: (561)436-5355 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) ADDITIONAL INFORMATION RQUIRED. THE PERMIT |
| APPLICATION UNDER THE HEADING DESCRIBE PROJECT IN |
| DETAIL, INDICATES DEMO OF INTERIOR CONCRETE FLOOR. |
| PLEASE PROVIDE WHERE THIS CONDITION EXIST. UNDER THE |
| EXPIRED PERMIT 09110339 PLAN REVIEW COMMENTS INDICATE |
| THE REPLACEMENT OR REPAIR OF 2X10 FLOOR JOIST, 3X8 GLUE |
| LAMS AND STEEL COLUMNS? SHEET 2.1 ALSO INDICATES |
| FRAMING OF FLOOR JOIST , GLUE-LAMS AND STEEL COLUMNS, |
| IS THE WORK DEPICTED PART OF THE WORK TO BE COVERED |
| UNDER THIS PERMIT OR SHOULD THE WORK DEPICTED STRUCKNOT |
| PART OF THIS PERMIT? |
| |
| 2) PLANS 2.1 PROVIDE OCCUPANCY SEPERATION BETWEEN THE |
| FIRST FLOOR AND SECOND FLOOR SINCE THE FIRST FLOOR IS |
| CONSIDERED BUSINESS AND THE SECOND AS RESIDENTIAL. |
| 2007/09 FBC-B TABLE 503. PLEASE PROVIDE FIRE RATED |
| ASSEMBLIES FOR THROUGH PENETRATIONS. 712.4.1.1. |
| |
| 3) SHEET 1.1 INDICATES WIDER WINDOW OPENINGS WITH NEW |
| CELL INFILL, PLANS ALSO INDICATE ALSO LOCATED ON THIS |
| SHEET IS A NOTE FOR 2X BUCKS PER MANUFACTURERS |
| REQUIREMENTS, NO FASTENING INFORMATION SHILE ON SHEET |
| 2.1 DETAIL 3 THE DETAIL INDICATES THE USE OF 1X4 PT |
| BUCKS ATTACHED WITH CASE HARDENED NAILS AT 24" OC, BUT |
| NO SIZE IS PROVIDED FOR THE CASE HARDENED NAIL. |
| |
| 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 5) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)((B) WINDOWS & MULLIONS |
| |
| |
| 6) SHEET 1.1 BATHROOM WINDOW MAY OR MAY NOT NEED TO |
| MEET THE REQUIREMENTS OF 2007/09 FBC-B 2406.3 |