Plan Review Notes
Plan Review Notes For Permit 12010102
Permit Number 12010102
Review Stop M
Sequence Number 1
Notes
Date Text
2012-01-06 14:32:41PLANS DENIED
 1) REFER TO SECTION 507.16 PERFORMANCE TEST 2007 FBC
 (M),
 AND SECTION 507.16.1 CAPTURE AND CONTAINMENT TEST.
 2) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS ON
 SOLID FUEL COOKING EQUIPMENT WITH THE PLANS .
 3) REFER TO NFPA 96 FOR SOLID FUEL COOKING EQUIPMENT.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732