2012-01-11 07:26:082007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE SANITARY RISER DIAGRAM FOR BATH NUMBER 4 IS NOT
 CODE COMPLIANT. FBCR P3108.3 STATES THAT IN HORIZONTAL
 WET-VENT SYSTEMS, NOT MORE THAN ONE WET-VENTED FIXTURE
 DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED
 FIXTURE DRAIN CONNECTION. THE SHOWER AND WATER CLOSET
 BOTH ARE UP STREAM OF THE DRY-VENTED LAVATORY.
  