2012-01-09 17:46:3812010096
 6501 WASHINGTON RD.
 RESIDENTIAL ADDITION
  
 CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF
 ALL EXISTING SLEEPING AREAS. FBC R313
 MAIN ELECTRICAL DISCONNECTS MUST BE SERVICE RATED AND
 GROUPED IN ONE LOCATION. PANEL BOARDS ARE MISLABELED.
 NEC 230.
 SHOW LOCATION OF THE NEW SERVICE. NEC 215.15
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 PROVIDE A SUMMARY LOAD CALCULATION VERIFYING THE NEW
 300 AMP SERVICE IS ADEQUATE. NEC 220.40
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT NEC 406.11
 PROVIDE A 20 AMPERE RATED BRANCH CIRCUIT FOR THE NEW
 BATHROOMS. NEC 210.11 (C) (3)
 A DISCONNECTING MEANS IS REQUIRED FOR THE AIR
 CONDITIONING UNITS. NEC 440.11
 THE ATTIC SPACE REQUIRES A WALL-SWITCH CONTROLLED
 LIGHTING OUTLET. A LIGHTING OUTLET IS REQUIRED IN THE
 ATTIC AT OR NEAR THE EQUIPMENT REQUIRING SERVICE. NEC
 210.70
  
  