Plan Review Notes For Permit 12010096 |
Permit Number |
12010096 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-09 17:46:38 | 12010096 | | 6501 WASHINGTON RD. | | RESIDENTIAL ADDITION | | | | CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF | | ALL EXISTING SLEEPING AREAS. FBC R313 | | MAIN ELECTRICAL DISCONNECTS MUST BE SERVICE RATED AND | | GROUPED IN ONE LOCATION. PANEL BOARDS ARE MISLABELED. | | NEC 230. | | SHOW LOCATION OF THE NEW SERVICE. NEC 215.15 | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND NEC 250.94 | | PROVIDE A SUMMARY LOAD CALCULATION VERIFYING THE NEW | | 300 AMP SERVICE IS ADEQUATE. NEC 220.40 | | ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC | | FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | NEW RECEPTACLES MUST BE TAMPER RESISTANT NEC 406.11 | | PROVIDE A 20 AMPERE RATED BRANCH CIRCUIT FOR THE NEW | | BATHROOMS. NEC 210.11 (C) (3) | | A DISCONNECTING MEANS IS REQUIRED FOR THE AIR | | CONDITIONING UNITS. NEC 440.11 | | THE ATTIC SPACE REQUIRES A WALL-SWITCH CONTROLLED | | LIGHTING OUTLET. A LIGHTING OUTLET IS REQUIRED IN THE | | ATTIC AT OR NEAR THE EQUIPMENT REQUIRING SERVICE. NEC | | 210.70 | | | | |
|