Plan Review Notes
Plan Review Notes For Permit 12010096
Permit Number 12010096
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-17 16:56:052007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED LESS THAN 700 FEET FROM THE
 INTER-COASTAL WATERWAY WHICH MAKES THE EXPOSURE
 CATEGORY C. SEE FBC R301.2.1.4.3.
  
 2) REVISE THE COMPONENT AND CLADDING PRESSURES ON SHEET
 ONE TO COMPLY WITH EXPOSURE CATEGORY C. SEE FBC
 R301.2.1.
  
 3) PLEASE HAVE THE STRUCTURAL ENGINEER REVIEW THE SOIL
 REPORT FROM D & N DRILLING AND ENGINEERING, INC. TO
 INSURE THAT THE FOOTING DESIGN IS ADEQUATE. THE SOIL
 ENGINEER RECOMMENDS 24" WIDE CONTINUOUS FOOTERS AND A
 MINIMUM OF 36" FOR INDIVIDUAL FOOTERS WITH A MINIMUM
 DEPTH OF 18" BELOW THE LOWEST BORDERING FINISHED GRADE.
  
 4) ON SHEET 4 THE DOOR BUCKS ARE SPECIFIED AS 2 X 4
 WHICH MAY NOT BE WIDE ENOUGH TO PROVIDE FULL SUPPORT OF
 THE DOOR FRAME AS REQUIRED BY FBC R613.6.1.1. PLEASE
 REVISE.
  
 5) FBC R308.4 REQUIRES GLAZING IN BATHROOM WINDOWS AND
 DOORS WHERE THE BOTTOM EDGE IS OF THE GLAZING IS LESS
 THAN 60 INCHES ABOVE ANY STANDING OR WALKING SURFACE TO
 BE SAFETY GLASS OR IMPACT RATED GLASS.
  
 6) SPECIFY THE TRUSS UPLIFT PRESSURES AND PROVIDE A
 TRUSS ANCHOR SCHEDULE ON THE PLANS. SEE FBC R802.1.6.5.
  
 7) SUBMIT TWO COMPLETE COPIES OF PRODUCT APPROVALS FOR
 THE NEW EXTERIOR DOORS, WINDOWS, STRUCTURAL MULLIONS
 AND ROOFING COVERING MATERIALS AS REQUIRED BY DCA 9N-3.
 IN ADDITION TO THE FLORIDA PRODUCT APPROVAL COVER
 SHEETS THAT WERE SUBMITTED, THE PRODUCT EVALUATIONS AND
 INSTALLATION INSTRUCTIONS ARE REQUIRED. THESE ARE
 AVAILABLE ON LINE AT
 WWW.FLORIDABUILDING.ORG/C/DEFAULT.ASPX .
  
 8) TWO SETS OF THE PRODUCT APPROVALS ARE REQUIRED FOR
 EACH DIFFERENT TYPE OF WINDOW OR DOOR. CITY AMENDMENTS
 106.1.
  
 9) IF HURRICANE PANELS ARE BEING USED, SUBMIT TWO SETS
 OF PRODUCT APPROVALS, KEY PLANS AND INSTALLATION
 SCHEDULES FOR THEM. DCA RULE 9N-3 AND FBC R301.2.1.2
 FOR INSTALLATION SCHEDULES SEE WWW.WPB.ORG/CONSTRUCTION
 /PDF/SCHEDULE_FOR_INSTALLATION.PDF.
  
 10) SPECIFY WHICH ONE OF THE ROOF TILE ATTACHMENT
 METHODS LISTED IN THE PRODUCT APPROVAL WILL BE USED. IF
 USING A MORTAR OR ADHESIVE SET SYSTEM SUBMIT PRODUCT
 APPROVALS FOR THE PRODUCT THAT WILL BE USED. DCA RULE
 9N-3.
  
 11) PROVIDE A DETAIL FOR THE SISTERED 2 X 4 TRUSS TAILS
 SHOWN ON THE WALL SECTIONS ON SHEET 7. FBC R801.2
  
 12) THE PLANS SPECIFY A NEW 4 X 4 STEEL COLUMN AT THE
 COVERED PATIO. PROVIDE A DETAIL FOR THE 4 X 4 STEEL
 COLUMN BASE AND CAP.
  