Plan Review Notes
Plan Review Notes For Permit 12010093
Permit Number 12010093
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-06 12:02:01RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- UNDERLAYMENT FLORIDA PRODUCT APPROVAL FL14317-R1
 SUBMITTED: ACCORDING TO LIMITATION 5.5.2.1 THE MAXIMUM
 DESIGN PRESSURE IS -45PSF FOR A DIRECT BOND DECK
 UNDERLAYMENT. DESIGN PRESSURES FOR THE PERIMETER AND
 CORNER AREAS ARE HIGHER FOR THIS BUILDING. THIS PRODUCT
 CAN'T NOT BE USED. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL ME:
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712