2012-01-12 13:52:45 | 901 45TH STREET - MAINTENANCE BUILDING |
| PERMIT #12010058 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PER FLORIDA STATUTES, FIRE SPRINKLER DRAWINGS AND |
| HYDRAULIC CALCULATIONS ARE REQUIRED TO BE SIGNED AND |
| SEALED BY A PROFESSIONAL ENGINEER FOR THE DESIGN OR |
| ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. |
| |
| SPRINKLER DESIGN SHALL CONFORM TO THE REQUIREMENTS OF |
| THE 2007 EDITION OF NFPA 13 AS OF JANUARY 1, 2012. |
| |
| SUBMIT HYDRAULIC CALCULATIONS FOR REVIEW AND PROVIDE |
| HYDRAULIC DESIGN PLACARD ON RISER. |
| |
| PROVIDE WATER SUPPLY INFORMATION (FIRE PUMP TEST OR |
| HYDRANT FLOW TEST, ETC.). |
| |
| INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS |
| FLOOR. |
| |
| PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| DEPARTMENT CONNECTION. |
| |
| THE 4-INCH STANDPIPE RISER ON THE EAST SIDE OF THE |
| BUILDING APPEARS TO BE SUPPLYING THE SPRINKLER SYSTEM; |
| HOWEVER, THERE ARE SPRINKLERS LOCATED BOTH UPSTREAM AND |
| DOWNSTREAM OF THE FLOOR CONTROL ASSEMBLY. PLEASE |
| EXPLAIN. |
| |
| TWO STORAGE ROOMS ON SHEET 2 DO NOT INDICATE THE |
| FINISHED CEILING TO BE RUN TIGHT TO THE BOTTOM OF THE |
| WOOD CEILING JOISTS. SPRINKLERS WILL BE REQUIRED IN THE |
| COMBUSTIBLE CONCEALED SPACE IF THE CEILING IS LOCATED |
| MORE THAN 6-INCHES BELOW THE JOISTS. VERIFY CEILING |
| ELEVATION IN RELATION TO THE JOISTS. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| |