2012-01-04 10:56:51 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) SECTION N1107.AB.1 OF THE 2007 ENERGY GLITCH | | AMENDMENTS REQUIRES THE HVAC EQUIPMENT TO BE SIZED | | BASED ON THE ORIENTATION OF THE BUILDING. WORST- CASE | | SIZING CALCULATIONS ARE NOT PERMITTED. PLEASE SUBMIT | | SITE SPECIFIC CALCULATIONS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|