2012-03-09 11:19:31200 CLEMATIS STREET
 PERMIT #11120544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - THE USE OF THE EXISTING NON-CONFORMING
 OPEN STAIR BETWEEN THE 1ST AND 2ND FLOOR IS CONSIDERED
 TO BE APPROVED; HOWEVER, THE FOLLOWING FIRE PROTECTION
 FEATURES SHALL BE INSTALLED:
  
 PER NFPA 13, CLOSELY SPACED SPRINKLERS (6'-0" SPACING)
 AND 18" TALL NON-COMBUSTIBLE DRAFT CURTAINS WILL BE
 REQUIRED AROUND THE PERIMETER OF THE FLOOR/CEILING
 OPENING BETWEEN THE 1ST AND 2ND FLOOR.
  
 REPLACE ANY STANDARD-RESPONSE TYPE SPRINKLERS WITH
 QUICK-RESPONSE TYPE SPRINKLERS.
  
 PROVIDE A COMPLETE SMOKE DETECTION SYSTEM (EXCLUDING
 KITCHEN AREA), COMPLIANT WITH NFPA 72, FOR THE
 BASEMENT, 1ST FLOOR AND 2ND FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE