Plan Review Notes For Permit 11120544 |
Permit Number |
11120544 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-03-09 11:19:31 | 200 CLEMATIS STREET | | PERMIT #11120544 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - THE USE OF THE EXISTING NON-CONFORMING | | OPEN STAIR BETWEEN THE 1ST AND 2ND FLOOR IS CONSIDERED | | TO BE APPROVED; HOWEVER, THE FOLLOWING FIRE PROTECTION | | FEATURES SHALL BE INSTALLED: | | | | PER NFPA 13, CLOSELY SPACED SPRINKLERS (6'-0" SPACING) | | AND 18" TALL NON-COMBUSTIBLE DRAFT CURTAINS WILL BE | | REQUIRED AROUND THE PERIMETER OF THE FLOOR/CEILING | | OPENING BETWEEN THE 1ST AND 2ND FLOOR. | | | | REPLACE ANY STANDARD-RESPONSE TYPE SPRINKLERS WITH | | QUICK-RESPONSE TYPE SPRINKLERS. | | | | PROVIDE A COMPLETE SMOKE DETECTION SYSTEM (EXCLUDING | | KITCHEN AREA), COMPLIANT WITH NFPA 72, FOR THE | | BASEMENT, 1ST FLOOR AND 2ND FLOOR. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE |
|