2012-02-15 09:37:42 | |
| FBC 2007 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. NOT COMPLIED AT THIS TIME: |
| THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR |
| WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT. |
| 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES |
| OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN |
| COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET |
| FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY |
| ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH |
| TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH |
| FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152 |
| M). |
| |
| (IF THE RESTROOMS THAT ARE SHOWN ON THE EXITING PLAN - |
| OPTION "B" ARE TO BE USED, PLEASE INCLUDE THE |
| CALCULATIONS FOR THE OCCUPANT LOAD BASED ON THE SECOND |
| FLOOR DINING AREA PLUS THE BUSINESS USE ON THAT FLOOR). |
| |
| 2. OK |
| |
| 3. BASEMENT LEVEL. SHEET A1.1 INDICATES |
| NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES |
| RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE |
| ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE |
| DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW |
| CONSTRUCTION (1) : |
| |
| THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN |
| ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH |
| LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 |
| INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] ... |
| |
| (FIGURE 30E SHOWS A CLEAR FLOOR SPACE OF 60" WIDE WITH |
| THE LAVATORY OUTSIDE OF THAT SPACE. THE NOTES FOR |
| FIGURE 30E ALSO STATE THAT THERE ARE MANY POSSIBLE |
| LOCATIONS FOR THE LAVATORY WITHIN THE TOILET STALL). |
| |
| 4. OK |
| GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS, |
| APPLICATION, AND REVIEWS ARE REQUIRED. |
| |
| 5. OK |
| |
| NEW NOTE: SOME METHOD OF KEEPING OIL OUT OF THE |
| SANITARY SEWER WILL BE REQUIRED FOR THE ELEVATOR SUMP |
| PUMP. THIS COULD BE ACCOMPLISHED WITH AN APPROVED OIL |
| SENSING SUMP CONTROL SYSTEM. |
| |