Plan Review Notes
Plan Review Notes For Permit 11120544
Permit Number 11120544
Review Stop P
Sequence Number 2
Notes
Date Text
2012-02-15 09:37:42 
 FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. NOT COMPLIED AT THIS TIME:
 THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR
 WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT.
 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN
 COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET
 FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY
 ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH
 TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH
 FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152
 M).
  
 (IF THE RESTROOMS THAT ARE SHOWN ON THE EXITING PLAN -
 OPTION "B" ARE TO BE USED, PLEASE INCLUDE THE
 CALCULATIONS FOR THE OCCUPANT LOAD BASED ON THE SECOND
 FLOOR DINING AREA PLUS THE BUSINESS USE ON THAT FLOOR).
  
 2. OK
  
 3. BASEMENT LEVEL. SHEET A1.1 INDICATES
 NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES
 RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE
 ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE
 DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW
 CONSTRUCTION (1) :
  
 THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] ...
  
 (FIGURE 30E SHOWS A CLEAR FLOOR SPACE OF 60" WIDE WITH
 THE LAVATORY OUTSIDE OF THAT SPACE. THE NOTES FOR
 FIGURE 30E ALSO STATE THAT THERE ARE MANY POSSIBLE
 LOCATIONS FOR THE LAVATORY WITHIN THE TOILET STALL).
  
 4. OK
 GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS,
 APPLICATION, AND REVIEWS ARE REQUIRED.
  
 5. OK
  
 NEW NOTE: SOME METHOD OF KEEPING OIL OUT OF THE
 SANITARY SEWER WILL BE REQUIRED FOR THE ELEVATOR SUMP
 PUMP. THIS COULD BE ACCOMPLISHED WITH AN APPROVED OIL
 SENSING SUMP CONTROL SYSTEM.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  