2012-02-13 12:19:34 | BUILDING PLAN REVIEW |
| PERMIT: 11120544 |
| ADD: 200 CLEMATIS ST |
| CONT: TBD |
| TEL: (269)599-1341 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| FEB. 13/2012 |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. |
| CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS |
| ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD: |
| |
| PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONCRETE RESTORATION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 3) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 4) COMPLIED. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| |
| 5) COMPLIED. SHEET A1 THE BUILDING CODE ANYLSIS |
| INDICATES THE WEST WALL BEING A 2 HR RATED WALL. THIS |
| WALL SHOULD BE A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE |
| 601, TABLE 602, < THAN 5'-0" FROM THE PROPERTY LINE. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT |
| STAIR WITH A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER |
| THE STAIR, PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE |
| USE OF THIS NEW AREA? |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) 2ND REQUEST, BASEMENT LEVEL. SHEET A1.1 INDICATES |
| NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES |
| RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE |
| ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE |
| DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW |
| CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS |
| SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT. |
| |
| 11) COMPLIED. |
| |
| 12) SECOND REQUEST. SHEET A2, A5 & S-1 SHOW INFILL OF |
| AN EXTERIOR BLOCK WALL. S1 ALSO INDICATES A CUT SECTION |
| C/S3 NO SUCH DETAIL PROVIDING INFORMATION ON THE |
| VERTICAL AND HORIZONTAL REINFORCEMENT FOR THE INFILL |
| BLOCK. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 13) COMPLIED. |
| |
| 14)COMPLIED. |
| |
| 15) COMPLIED. |
| |
| 16)COMPLIED. |
| |
| 17) SEMI -COMPLIED. A6.1 & S-2 THE ELEVATOR DESIGN DOES |
| NOT INDICATE WHAT TYPE OF SYSTEM IS TO DESIGNED AT THIS |
| POINT, NOTE DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4 |
| NOR DOES THE PLANS INDICATE COMPLIANCE WITH 3007.1 |
| ELEVATOR ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY |
| HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT. |
| 2ND REVIEW COMMENT- THE REQUIREMENT FOR THE SUMP IS |
| LOCATED WITHIN THE BLDG CODE, THE SIZING OF THE SUMP |
| PIT IS LOCATED WITH IN THE PLUMBING CODE REQUIRING A 18 |
| INCH WIDE BY 24 INCH DEEP PIT. PLEASE BE AWARE THAT IF |
| A HYDROLIC ELEVATOR IS INSTALLED, IF THERE IS A |
| HYDROLIC LEAK IT MAY NOT GO TO SANITARY, PLEASE SEE |
| PLUMBING COMMENTS. |
| |
| 18) COMPLIED. |
| |
| 19)COMPLIED. |
| |
| 20) COMPLIED. |
| |
| NEW COMMENTS |
| |
| 21) IN REGARDS TO THE 2ND FLOOR EXITING. 2007/09 EXIST |
| BLDG CODE 601.2 ALLOWS FOR AN EXISTING BUILDING TO BE |
| ALTERED OR PORTIONS THERE OF AND SHALL NOT BE ALTERED |
| SUCH THAT THE BUILDING BECOMES LESS SAFE. PLEASE |
| PROVIDE WHAT THTE OCCUPANT LOAD WOULD HAVE BEEN BEFORE |
| THE REMOVAL OF THE 2ND STORY RESTROOMS. WITH THE |
| RECONFIGURATION OF THE 2ND FLOOR IT WILL NEED TO BE |
| EQUAL TO OR LESS THAN THE OCCUPANT LOAD FOR THE 2ND |
| FLOOR BEFORE THE REMODELING TOOK PLACE.THE EXISTING |
| BLDG CODE 705.3 NUMBER OF EXITS . THE NUMBER OF EXITS |
| SHALL BE IN ACCORDANCE WITH THE APPROPRIATE SECTIONS OF |
| THE FLORIDA FIRE PREVENTION CODE. |
| |
| 22) THE NEW STAIRWWELL TO THE BASEMENT IS CONSIDERED |
| NEW WORK AND WILL NEED TO MEET THE REQUIREMENTS FOR NEW |
| CONSTRUCTION. 2007 EXISTING BUILDING CODE LEVEL II |
| 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. 2007/09 |
| FBC-B 1020.1 VERTICAL SHAFT ENCLOSURES. |
| |
| 23) OUTSWING KAWNEER STORE FRONT DOORS NOA 09-0129.01 |
| GLAZING TYPE NOT PROVIDED TYPE A & B DO NOT MEET |
| PRESSURES CLASS C & D DO MEET PRESSURERS? PLEASE |
| PROVIDE ADDITIONAL INFORMATION AS TO WHICH GLAZING |
| SYSTEM TO BE INSTALLED. |
| |
| |