Plan Review Notes
Plan Review Notes For Permit 11120544
Permit Number 11120544
Review Stop B
Sequence Number 2
Notes
Date Text
2012-02-13 12:19:34BUILDING PLAN REVIEW
 PERMIT: 11120544
 ADD: 200 CLEMATIS ST
 CONT: TBD
 TEL: (269)599-1341
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 FEB. 13/2012
 2ND REVIEW
 ACTION: DENIED
  
 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS
 ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) COMPLIED. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
  
 5) COMPLIED. SHEET A1 THE BUILDING CODE ANYLSIS
 INDICATES THE WEST WALL BEING A 2 HR RATED WALL. THIS
 WALL SHOULD BE A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE
 601, TABLE 602, < THAN 5'-0" FROM THE PROPERTY LINE.
  
 6) COMPLIED.
  
 7) COMPLIED. BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT
 STAIR WITH A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER
 THE STAIR, PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE
 USE OF THIS NEW AREA?
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) 2ND REQUEST, BASEMENT LEVEL. SHEET A1.1 INDICATES
 NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES
 RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE
 ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE
 DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW
 CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS
 SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT.
  
 11) COMPLIED.
  
 12) SECOND REQUEST. SHEET A2, A5 & S-1 SHOW INFILL OF
 AN EXTERIOR BLOCK WALL. S1 ALSO INDICATES A CUT SECTION
 C/S3 NO SUCH DETAIL PROVIDING INFORMATION ON THE
 VERTICAL AND HORIZONTAL REINFORCEMENT FOR THE INFILL
 BLOCK. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 13) COMPLIED.
  
 14)COMPLIED.
  
 15) COMPLIED.
  
 16)COMPLIED.
  
 17) SEMI -COMPLIED. A6.1 & S-2 THE ELEVATOR DESIGN DOES
 NOT INDICATE WHAT TYPE OF SYSTEM IS TO DESIGNED AT THIS
 POINT, NOTE DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4
 NOR DOES THE PLANS INDICATE COMPLIANCE WITH 3007.1
 ELEVATOR ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY
 HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT.
 2ND REVIEW COMMENT- THE REQUIREMENT FOR THE SUMP IS
 LOCATED WITHIN THE BLDG CODE, THE SIZING OF THE SUMP
 PIT IS LOCATED WITH IN THE PLUMBING CODE REQUIRING A 18
 INCH WIDE BY 24 INCH DEEP PIT. PLEASE BE AWARE THAT IF
 A HYDROLIC ELEVATOR IS INSTALLED, IF THERE IS A
 HYDROLIC LEAK IT MAY NOT GO TO SANITARY, PLEASE SEE
 PLUMBING COMMENTS.
  
 18) COMPLIED.
  
 19)COMPLIED.
  
 20) COMPLIED.
  
 NEW COMMENTS
  
 21) IN REGARDS TO THE 2ND FLOOR EXITING. 2007/09 EXIST
 BLDG CODE 601.2 ALLOWS FOR AN EXISTING BUILDING TO BE
 ALTERED OR PORTIONS THERE OF AND SHALL NOT BE ALTERED
 SUCH THAT THE BUILDING BECOMES LESS SAFE. PLEASE
 PROVIDE WHAT THTE OCCUPANT LOAD WOULD HAVE BEEN BEFORE
 THE REMOVAL OF THE 2ND STORY RESTROOMS. WITH THE
 RECONFIGURATION OF THE 2ND FLOOR IT WILL NEED TO BE
 EQUAL TO OR LESS THAN THE OCCUPANT LOAD FOR THE 2ND
 FLOOR BEFORE THE REMODELING TOOK PLACE.THE EXISTING
 BLDG CODE 705.3 NUMBER OF EXITS . THE NUMBER OF EXITS
 SHALL BE IN ACCORDANCE WITH THE APPROPRIATE SECTIONS OF
 THE FLORIDA FIRE PREVENTION CODE.
  
 22) THE NEW STAIRWWELL TO THE BASEMENT IS CONSIDERED
 NEW WORK AND WILL NEED TO MEET THE REQUIREMENTS FOR NEW
 CONSTRUCTION. 2007 EXISTING BUILDING CODE LEVEL II
 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. 2007/09
 FBC-B 1020.1 VERTICAL SHAFT ENCLOSURES.
  
 23) OUTSWING KAWNEER STORE FRONT DOORS NOA 09-0129.01
 GLAZING TYPE NOT PROVIDED TYPE A & B DO NOT MEET
 PRESSURES CLASS C & D DO MEET PRESSURERS? PLEASE
 PROVIDE ADDITIONAL INFORMATION AS TO WHICH GLAZING
 SYSTEM TO BE INSTALLED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  