Plan Review Notes
Plan Review Notes For Permit 11120544
Permit Number 11120544
Review Stop P
Sequence Number 1
Notes
Date Text
2012-01-12 11:28:24 
 FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR
 WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT.
 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES
 OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN
 COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET
 FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY
 ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH
 TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH
 FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152
 M).
  
 2. THE MENS ROOM IN THE BASEMENT LEVEL HAS MORE
 FIXTURES THAN THE WOMENS ROOM. WHILE THE RESTAURANT IS
 LICENSED UNDER F.S. 509, PLEASE SEE THE EXCEPTION FOR
 403.1.1 POTTY PARITY. THE SAME NUMBER OF WATER CLOSETS
 IS REQUIRED FOR WOMEN AS THE COMBINED W.C AND URINALS
 FOR MEN:
  
 403.1.1 POTTY PARITY. IN ASSEMBLY OCCUPANCIES,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS AND URINALS PROVIDED
 FOR MEN, UNLESS THESE ARE TWO OR FEWER SUCH FIXTURES
 FOR MEN, IN ACCORDANCE WITH ?553.86, FLORIDA STATUTES.
  
 EXCEPTION: THIS SECTION DOES NOT APPLY TO
 ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA
 STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING
 OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150
 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME
 NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
  
 3. THE ADA STALLS WILL REQUIRE A LAV INSTALLED IN THE
 STALL PER 11-4.17 EXCEPTION (1) SEE FIGURE 30(E)
  
 4. GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS,
 APPLICATION, AND REVIEWS ARE REQUIRED.
  
 5. SHEET P5 - HOSE BIBBS REQUIRE SEPARATE SHUT OFF
 VALVES:
 606.2 LOCATION OF SHUTOFF VALVES.
 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  
  
  