2012-01-12 11:28:24 | |
| FBC 2007 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR |
| WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT. |
| 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES |
| OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN |
| COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET |
| FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY |
| ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH |
| TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH |
| FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152 |
| M). |
| |
| 2. THE MENS ROOM IN THE BASEMENT LEVEL HAS MORE |
| FIXTURES THAN THE WOMENS ROOM. WHILE THE RESTAURANT IS |
| LICENSED UNDER F.S. 509, PLEASE SEE THE EXCEPTION FOR |
| 403.1.1 POTTY PARITY. THE SAME NUMBER OF WATER CLOSETS |
| IS REQUIRED FOR WOMEN AS THE COMBINED W.C AND URINALS |
| FOR MEN: |
| |
| 403.1.1 POTTY PARITY. IN ASSEMBLY OCCUPANCIES, |
| RESTROOMS WHICH ARE OPEN TO THE PUBLIC MUST HAVE A |
| RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE |
| COMBINED TOTAL OF WATER CLOSETS AND URINALS PROVIDED |
| FOR MEN, UNLESS THESE ARE TWO OR FEWER SUCH FIXTURES |
| FOR MEN, IN ACCORDANCE WITH ?553.86, FLORIDA STATUTES. |
| |
| EXCEPTION: THIS SECTION DOES NOT APPLY TO |
| ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA |
| STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING |
| OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 |
| PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME |
| NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL |
| OF WATER CLOSETS AND URINALS FOR MEN. |
| |
| 3. THE ADA STALLS WILL REQUIRE A LAV INSTALLED IN THE |
| STALL PER 11-4.17 EXCEPTION (1) SEE FIGURE 30(E) |
| |
| 4. GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS, |
| APPLICATION, AND REVIEWS ARE REQUIRED. |
| |
| 5. SHEET P5 - HOSE BIBBS REQUIRE SEPARATE SHUT OFF |
| VALVES: |
| 606.2 LOCATION OF SHUTOFF VALVES. |
| 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER |
| THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| |