| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| I. GENERAL |
| IN ADDITION TO THE FLORIDA BUILDING CODE, THE FIRE |
| PROTECTION AND LIFE SAFETY DESIGN SHALL CONFORM TO THE |
| 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE (2009 |
| EDITION OF NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS). |
| |
| ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS ARE |
| REQUIRED FOR THE MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND FIRE ALARM SYSTEM. |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| CONTRAST THE BACKGROUND. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE |
| PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO |
| RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE |
| PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN |
| ENTRANCE, AND MAIN ENTRANCE ONLY, IS PERMITTED TO HAVE |
| AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE |
| LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED |
| LOCK. |
| |
| PENETRATIONS INTO THE PROTECTED STAIR ENCLOSURES ARE |
| LIMITED TO EQUIPMENT ESSENTIAL TO THE FUNCTION OF THE |
| STAIR. THE CURRENT MEP DRAWINGS SHOW DRAIN LINES, COLD |
| WATER LINES, ELECTRICAL LINES ETC. THAT WILL NOT BE |
| PERMITTED. |
| |
| EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| FEET ON CENTER. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| |
| II. BASEMENT |
| THE TWO BASEMENT STAIR DOORS SHOULD HAVE A 1-HOUR FIRE |
| RATING IN LIEU OF 45-MINUTES PER TABLE 8.3.4.2 (NFPA |
| 101). |
| |
| OPENINGS INTO A STAIR ENCLOSURE ARE LIMITED TO NORMALLY |
| OCCUPIED SPACES; HOWEVER, SECTION 7.1.3.2.1[8][B] (NFPA |
| 101) PERMITS MECHANICAL ROOMS PROVIDED THE SPACE DOES |
| NOT CONTAIN FUEL-FIRE EQUIPMENT OR STORAGE OF |
| COMBUSTIBLES. NO EXEMPTION IS MADE FOR ELECTRICAL |
| ROOMS. |
| |
| FOR STAIR #113, THE ENTIRE AREA ON THE LEVEL OF |
| DISCHARGE SHALL BE SEPARATED FROM AREAS BELOW BY A |
| 1-HOUR FIRE RESISTANCE RATING PER SECTION 7.7.2.6 (NFPA |
| 101). |
| |
| INDICATE THE SIGNAGE AND COMMUNCATION SYSTEM THAT WILL |
| BE PROVIDED FOR THE AREA OF REFUGE. |
| |
| INDICATE THE REFRIGERANT AND THE NUMBER OF POUNDS |
| ASSOCIATED WITH THE WALK-IN BEER COOLER. |
| |
| III. SECOND FLOOR |
| THE SECOND FLOOR REQUIRES TWO FIRE-RATED EXIT |
| ENCLOSURES. THE SECOND FLOOR IS TOO LARGE TO BE |
| CONSIDERED A MEZZANINE WHEREBY AN OPEN EXIT ACCESS |
| STAIR WOULD BE ACCEPTABLE. FOR STAIR #112, THE ENTIRE |
| AREA ON THE LEVEL OF DISCHARGE SHALL BE SEPARATED FROM |
| AREAS BELOW BY A 1-HOUR FIRE RESISTANCE RATING PER |
| SECTION 7.7.2.6 (NFPA 101). INDICATE IF THE EXISTING |
| STAIR (NIC) DISCHARGES TO THE EXTERIOR OR INTERIOR OF |
| THE BUILDING. |
| |
| THE SOUTH WALL OF MAIN DINING #201 IS INDICATED AS A |
| 1-HOUR WALL. ALL THE OTHER WALLS AND FLOOR ARE RATED AT |
| TWO-HOURS. INDICATE IF THE 1-HOUR WALL WILL BE UPGRADED |
| TO A TWO-HOUR WALL. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| |