2012-01-09 11:22:0311120544
 200 CLEMATIS STREET
 NEW RESTAURANT & BAR (BAR LOUIE)
  
 RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST BE
 GFCI PROTECTED. NEC 210.8
 A GFCI GENERAL PURPOSE RECEPTACLE MUST BE INSTALLED AT
 AN ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63
 THE ELEVATOR EQUIPMENT ROOM REQUIRES A GFCI PROTECTED
 RECEPTACLE OUTLET. NEC 620.22, 620.85
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
 ALL DECORATIVE FIXTURES MUST BE LISTED BY AN APPROVED
 TESTING AGENCY. NEC 110.3
 PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES
 AND LIGHTING ARRAYS WEIGHING MORE THAN 50 POUNDS. NEC
 410.36, 314.27
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOMS. NEC 110.22, 110.16, 701.9
  