Plan Review Notes For Permit 11120544 |
Permit Number |
11120544 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-09 11:22:03 | 11120544 | | 200 CLEMATIS STREET | | NEW RESTAURANT & BAR (BAR LOUIE) | | | | RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST BE | | GFCI PROTECTED. NEC 210.8 | | A GFCI GENERAL PURPOSE RECEPTACLE MUST BE INSTALLED AT | | AN ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR | | CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63 | | THE ELEVATOR EQUIPMENT ROOM REQUIRES A GFCI PROTECTED | | RECEPTACLE OUTLET. NEC 620.22, 620.85 | | PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC 13-415 ABC.5 | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | EXISTING BUILDING CODE 711.1 | | ALL DECORATIVE FIXTURES MUST BE LISTED BY AN APPROVED | | TESTING AGENCY. NEC 110.3 | | PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES | | AND LIGHTING ARRAYS WEIGHING MORE THAN 50 POUNDS. NEC | | 410.36, 314.27 | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | ROOMS. NEC 110.22, 110.16, 701.9 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|