2012-01-03 16:56:31 | BUILDING PLAN REVIEW |
| PERMIT: 11120544 |
| ADD: 200 CLEMATIS ST |
| CONT: TBD |
| TEL: (269)599-1341 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. |
| CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| BEFORE THE PERMIT MAY BE ISSUED. |
| |
| A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS |
| ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD: |
| |
| PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONCRETE RESTORATION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 3) THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 4) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| |
| 5) SHEET A1 THE BUILDING CODE ANYLSIS INDICATES THE |
| WEST WALL BEING A 2 HR RATED WALL. THIS WALL SHOULD BE |
| A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE 601, TABLE |
| 602, < THAN 5'-0" FROM THE PROPERTY LINE. |
| |
| 6) BASEMENT LEVEL. SHEET A1.1INDICATES NEW WALL |
| CONSTRUCTION IN THE AREAS OF ROOM # 107 ELEVATOR |
| EQUIPMENT ROOM & ROOM # 106 AN EXISTING MECHANICAL & |
| ELECTRIC ROOM. THE DEMOLITION PLAN D1.1 DOES NOT |
| INDICATE ANY REMOVAL OF ANY WALLS IN THIS AREA, ONLY |
| THE REMOVAL OF A RAISED PLATFORM. THE FBC-B 1020.1.1 |
| OPENINGS AND PENETRATIONS INTO VERTICAL EXITS STAIRS, |
| THE OBJECTIVE IS TO MINIMIZE THE POSSIBILITY OF FIRE |
| SPREADING INTO THE EXIT ENCLOSURE AND ENDANGERING THE |
| OCCUPANTS OR EVEN PREVENTING THE USE OF THE EXIT AT A |
| POINT OF TIME WHEN IT IS NEEDED THE MOST. THE CODE |
| COMMENTARY LIST SPACES THAT ARE NOT NORMALLY OCCUPIED |
| INCLUDE, BUT NOT LIMITED TO, |
| TOILET ROOMS, ELECTRICAL/ MECHANICAL ROOMS AND |
| JANITORIAL CLOSETS. |
| |
| 7) BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT STAIR WITH |
| A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER THE STAIR, |
| PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE USE OF |
| THIS NEW AREA? |
| |
| 8) BASEMENT LEVEL. SHEET A1.1 THE PLANS INDICATE A TWO |
| HOUR RATED STAIRWAY WITH THE NEW WALLS BEING A 1 HOUR |
| CONSTRUCTION, THIS STAIRWAY IS LESS THAN 4 STORIES ONLY |
| REQUIRING A 1 HOUR ENCLOSURE. WITHIN THIS STAIRWAY THE |
| PLANS INDICATE THE USE OF A AREA OF RESCUE ASSISTANCE, |
| THE PLANS DO NOT PROVIDE THE WIDTH OF THE EXISTING |
| STAIR, NOR IF THERE IS A CENTER HANDRAIL EXISTING IN |
| THIS STAIR. WHEN ADDING A AREA OF RESCUE ASSISTANCE |
| PLEASE BE AWARE A MINUMUM CLEAR WIDTH OF 48 INCHES |
| BETWEEN HANDRAILS. |
| 2007/09 FBC-B 11-4.3.11.3. |
| |
| 9) BASEMENT LEVEL. SHEET A1 AND SHEET A1.1 BOTH |
| INDICATE NEW WALK IN COOLERS AND FREEZERS, WILL REQUIRE |
| SEPERATE PERMITS AND REVIEWS, AT TIME OF APPLICATION |
| PLEASE PROVIDE DOCUMENTATION OF FBC-B 2603.4.1.2. |
| |
| 10) BASEMENT LEVEL. SHEET A1.1 INDICATES NEW GANGED |
| RESTROOM STALLS FOR BOTH THE MENS AND LADIES RESTROOMS. |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW |
| CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS |
| SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT. |
| |
| 11) SHEET A2 INDICATES THE USE OF LULA LIFTS OR WHEEL |
| CHAIR PLATFORM LIFTS, PLEASE PROVIDE COMPLIANCE WITH |
| 11-4.11.2 ASME A17.1 . |
| |
| 12) SHEET A2, A5 & S-1 SHOW INFILL OF AN EXTERIOR BLOCK |
| WALL. S1 ALSO INDICATES A CUT SECTION C/S3 NO SUCH |
| DETAIL PROVIDING INFORMATION ON THE VERTICAL AND |
| HORIZONTAL REINFORCEMENT FOR THE INFILL BLOCK. 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 13) A4.1 THE 2ND FLOOR INDICATES WHAT APPEARS TO BE A |
| TV WALL MOUNTED SCREEN THAT BLOCKS THE EGRESS DOOR. |
| 11-4.4 PROTRUDING OBJECTS. |
| |
| 14) SHEET A6 & A6.1 DECRATIVE WALL SCONCES IF ON AN |
| ACCESSIBLE PATH PLEASE PROVIDE COMPLIANCE WWITH 11-4.4 |
| PROTRUDING OBJECTS, THIS WILL ALSO BE REVIEWED WITHIN |
| THE STAIRS. |
| |
| 15) SHEET A6 FURNISHINGS F4A BACK AND SEATS OF SEATS |
| AND F41 CURTAINS, PLEASE PROVIDE THE FLAME SPREAD AND |
| SMOKE DEVELOPMENT FOR THESE FINISHES. 2007/09 |
| FBC-B 803.1 & 803.5. |
| |
| 16) A6.1 PLEASE PROVIDE THE CORRECT RISE AND RUN FOR |
| THE NEW STAIRS, RISE IS SHOWN AS 11 1/2 INCHES. |
| FBC-B1009.3. |
| |
| 17) A6.1 & S-2 THE ELEVATOR DESIGN DOES NOT INDICATE |
| WHAT TYPE OF SYSSTEM IS TO DESIGNED AT THIS POINT, NOTE |
| DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4 NOR DOES |
| THE PLANS INDICATE COMPLIANCE WITH 3007.1 ELEVATOR |
| ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY |
| HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT. |
| |
| 18) A7 DETAAIL A713 ACCESSBILE LAV, 11-19.2 HEIGHT MAX |
| 34 INCHES. PLEASE SEE DIMENSIONS TOTALING TO 35 INCHES |
| VS 34 INCHES. |
| |
| 19) SHEET A13 INDICATES THE USE OF WOOD BUCKS FOR |
| WINDOW AAND DOOR ATTACHMENT, THE PRODUCT APPROVALS DO |
| NOT PROVIDE A FASTENING SCHEDULE FOR WOOD SUB-BUCKS |
| FBC 1609 . PLANS ARE NOT CLEAR IF THE USE OF WOOD BUCKS |
| WILL BE ATTACHED TO THE STEEL TS 10"X6" HEADER? THE |
| PRODUCT APPROVALS MAY NOT PROVIDE FASTENING OF THE |
| PRODUCT TO THE 5/16 INCH TUBE STEEL, PLEASE PROVIDE |
| TYPE OF FASTENERS FOR THIS APPLICATION. COMPONENTS & |
| CLADDING. |
| |
| 20) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS |
| PROVIDE WIND DESIGN CRITERIA, SINCE THIS BUILDING IS |
| OVER 60'-0" IN HEIGHT ASCE 7 AND EXPOSURE "C" WILL NEED |
| TO BE CONSIDERED FOR THE DESIGN FACTORS. PLEASE PROVIDE |
| THE POSITIVE ? NEGATIVE PRESSURES FOR THE INTERIOR AND |
| END ZONES FOR THIS PROJECT. PRODUCT APPROVALS SUBMITTED |
| CAN NOT BE CHECKED FOR COMPLIANCE UNTIL THE PRESSUES |
| ARE PROVIDED AND TYPE OF GLAZING IS PROVIDED SINCE THE |
| PRESSURES VARY WITH EACH GLAZING SYSTEM. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |