2012-01-03 16:56:31BUILDING PLAN REVIEW
 PERMIT: 11120544
 ADD: 200 CLEMATIS ST
 CONT: TBD
 TEL: (269)599-1341
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS
 ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
  
 5) SHEET A1 THE BUILDING CODE ANYLSIS INDICATES THE
 WEST WALL BEING A 2 HR RATED WALL. THIS WALL SHOULD BE
 A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE 601, TABLE
 602, < THAN 5'-0" FROM THE PROPERTY LINE.
  
 6) BASEMENT LEVEL. SHEET A1.1INDICATES NEW WALL
 CONSTRUCTION IN THE AREAS OF ROOM # 107 ELEVATOR
 EQUIPMENT ROOM & ROOM # 106 AN EXISTING MECHANICAL &
 ELECTRIC ROOM. THE DEMOLITION PLAN D1.1 DOES NOT
 INDICATE ANY REMOVAL OF ANY WALLS IN THIS AREA, ONLY
 THE REMOVAL OF A RAISED PLATFORM. THE FBC-B 1020.1.1
 OPENINGS AND PENETRATIONS INTO VERTICAL EXITS STAIRS,
 THE OBJECTIVE IS TO MINIMIZE THE POSSIBILITY OF FIRE
 SPREADING INTO THE EXIT ENCLOSURE AND ENDANGERING THE
 OCCUPANTS OR EVEN PREVENTING THE USE OF THE EXIT AT A
 POINT OF TIME WHEN IT IS NEEDED THE MOST. THE CODE
 COMMENTARY LIST SPACES THAT ARE NOT NORMALLY OCCUPIED
 INCLUDE, BUT NOT LIMITED TO,
 TOILET ROOMS, ELECTRICAL/ MECHANICAL ROOMS AND
 JANITORIAL CLOSETS.
  
 7) BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT STAIR WITH
 A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER THE STAIR,
 PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE USE OF
 THIS NEW AREA?
  
 8) BASEMENT LEVEL. SHEET A1.1 THE PLANS INDICATE A TWO
 HOUR RATED STAIRWAY WITH THE NEW WALLS BEING A 1 HOUR
 CONSTRUCTION, THIS STAIRWAY IS LESS THAN 4 STORIES ONLY
 REQUIRING A 1 HOUR ENCLOSURE. WITHIN THIS STAIRWAY THE
 PLANS INDICATE THE USE OF A AREA OF RESCUE ASSISTANCE,
 THE PLANS DO NOT PROVIDE THE WIDTH OF THE EXISTING
 STAIR, NOR IF THERE IS A CENTER HANDRAIL EXISTING IN
 THIS STAIR. WHEN ADDING A AREA OF RESCUE ASSISTANCE
 PLEASE BE AWARE A MINUMUM CLEAR WIDTH OF 48 INCHES
 BETWEEN HANDRAILS.
 2007/09 FBC-B 11-4.3.11.3.
  
 9) BASEMENT LEVEL. SHEET A1 AND SHEET A1.1 BOTH
 INDICATE NEW WALK IN COOLERS AND FREEZERS, WILL REQUIRE
 SEPERATE PERMITS AND REVIEWS, AT TIME OF APPLICATION
 PLEASE PROVIDE DOCUMENTATION OF FBC-B 2603.4.1.2.
  
 10) BASEMENT LEVEL. SHEET A1.1 INDICATES NEW GANGED
 RESTROOM STALLS FOR BOTH THE MENS AND LADIES RESTROOMS.
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW
 CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS
 SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT.
  
 11) SHEET A2 INDICATES THE USE OF LULA LIFTS OR WHEEL
 CHAIR PLATFORM LIFTS, PLEASE PROVIDE COMPLIANCE WITH
 11-4.11.2 ASME A17.1 .
  
 12) SHEET A2, A5 & S-1 SHOW INFILL OF AN EXTERIOR BLOCK
 WALL. S1 ALSO INDICATES A CUT SECTION C/S3 NO SUCH
 DETAIL PROVIDING INFORMATION ON THE VERTICAL AND
 HORIZONTAL REINFORCEMENT FOR THE INFILL BLOCK. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 13) A4.1 THE 2ND FLOOR INDICATES WHAT APPEARS TO BE A
 TV WALL MOUNTED SCREEN THAT BLOCKS THE EGRESS DOOR.
 11-4.4 PROTRUDING OBJECTS.
  
 14) SHEET A6 & A6.1 DECRATIVE WALL SCONCES IF ON AN
 ACCESSIBLE PATH PLEASE PROVIDE COMPLIANCE WWITH 11-4.4
 PROTRUDING OBJECTS, THIS WILL ALSO BE REVIEWED WITHIN
 THE STAIRS.
  
 15) SHEET A6 FURNISHINGS F4A BACK AND SEATS OF SEATS
 AND F41 CURTAINS, PLEASE PROVIDE THE FLAME SPREAD AND
 SMOKE DEVELOPMENT FOR THESE FINISHES. 2007/09
 FBC-B 803.1 & 803.5.
  
 16) A6.1 PLEASE PROVIDE THE CORRECT RISE AND RUN FOR
 THE NEW STAIRS, RISE IS SHOWN AS 11 1/2 INCHES.
 FBC-B1009.3.
  
 17) A6.1 & S-2 THE ELEVATOR DESIGN DOES NOT INDICATE
 WHAT TYPE OF SYSSTEM IS TO DESIGNED AT THIS POINT, NOTE
 DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4 NOR DOES
 THE PLANS INDICATE COMPLIANCE WITH 3007.1 ELEVATOR
 ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY
 HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT.
  
 18) A7 DETAAIL A713 ACCESSBILE LAV, 11-19.2 HEIGHT MAX
 34 INCHES. PLEASE SEE DIMENSIONS TOTALING TO 35 INCHES
 VS 34 INCHES.
  
 19) SHEET A13 INDICATES THE USE OF WOOD BUCKS FOR
 WINDOW AAND DOOR ATTACHMENT, THE PRODUCT APPROVALS DO
 NOT PROVIDE A FASTENING SCHEDULE FOR WOOD SUB-BUCKS
 FBC 1609 . PLANS ARE NOT CLEAR IF THE USE OF WOOD BUCKS
 WILL BE ATTACHED TO THE STEEL TS 10"X6" HEADER? THE
 PRODUCT APPROVALS MAY NOT PROVIDE FASTENING OF THE
 PRODUCT TO THE 5/16 INCH TUBE STEEL, PLEASE PROVIDE
 TYPE OF FASTENERS FOR THIS APPLICATION. COMPONENTS &
 CLADDING.
  
 20) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS
 PROVIDE WIND DESIGN CRITERIA, SINCE THIS BUILDING IS
 OVER 60'-0" IN HEIGHT ASCE 7 AND EXPOSURE "C" WILL NEED
 TO BE CONSIDERED FOR THE DESIGN FACTORS. PLEASE PROVIDE
 THE POSITIVE ? NEGATIVE PRESSURES FOR THE INTERIOR AND
 END ZONES FOR THIS PROJECT. PRODUCT APPROVALS SUBMITTED
 CAN NOT BE CHECKED FOR COMPLIANCE UNTIL THE PRESSUES
 ARE PROVIDED AND TYPE OF GLAZING IS PROVIDED SINCE THE
 PRESSURES VARY WITH EACH GLAZING SYSTEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676