Plan Review Notes For Permit 11120529 |
Permit Number |
11120529 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-19 16:47:16 | 11120529 | | 710 43RD ST. | | RESIDENTIAL BATH ADDITION | | | | SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED. | | PLEASE PROVIDE THE FOLLOWING: | | | | INDICATE THE SIZE AND LOCATION OF THE EXISTING | | ELECTRICAL PANEL. PROVIDE A PANEL SCHEDULE AND LOAD | | CALCULATION. SHOW THE SERVICE LOCATION, FEEDER SIZE AND | | EXISTING MAIN BREAKER. IF THIS IS A NEW SERVICE | | ADDITIONAL INFORMATION IS NEEDED. NEC 215.5 | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | RESISTANT. NEC 406.11 | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | 210.12 | | BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH CIRCUIT. | | NEC 210.11 (C) (3) | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|