Plan Review Notes
Plan Review Notes For Permit 11120529
Permit Number 11120529
Review Stop E
Sequence Number 1
Notes
Date Text
2012-01-19 16:47:1611120529
 710 43RD ST.
 RESIDENTIAL BATH ADDITION
  
 SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED.
 PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE AND LOCATION OF THE EXISTING
 ELECTRICAL PANEL. PROVIDE A PANEL SCHEDULE AND LOAD
 CALCULATION. SHOW THE SERVICE LOCATION, FEEDER SIZE AND
 EXISTING MAIN BREAKER. IF THIS IS A NEW SERVICE
 ADDITIONAL INFORMATION IS NEEDED. NEC 215.5
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH CIRCUIT.
 NEC 210.11 (C) (3)
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
  