2012-01-19 09:17:15 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM |
| BEACH COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES |
| ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF |
| PAID RECEIPT IF FEES ARE DUE. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF CHAPTER 13 FLORIDA RESIDENTIAL CODE. |
| |
| 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) WINDOWS AS SHOWN ON PLANS. |
| |
| B) EXTERIOR DOORS AS SHOWN ON PLANS. |
| |
| C) FLAT ROOF ASSEMBLY. AND, PLEASE SPECIFY WHICH |
| APPROVED ASSEMBLY IS GOING TO BE INSTALLED. ALSO, |
| PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| PERIMETER AND CORNER AREAS. NOTE: IF THE PRODUCT |
| APPROVAL SUBMITTED REQUIRES SIGNED AND SEALED |
| CALCULATIONS, THEN THOSE CALCULATIONS NEED TO BE SIGNED |
| AND SEALED. |
| |
| D) HURRICANE SHUTTERS IF THE DOORS AND WINDOWS PRODUCT |
| APPROVALS SUBMITTED DON'T HAVE IMPACT GLASS. AND, |
| PROVIDE A COMPLETE SHUTTERS INSTALLATION SCHEDULE. |
| |
| E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. |
| |
| 4- PROVIDE COMPLETE ROOF FRAMING PLAN. SHOW ALL FRAMING |
| MEMBERS SIZES AND CONNECTORS. SPECIFY ATTACHMENT TO |
| EXISTING ROOF. SPECIFY ROOF SLOPE. ETC. SEC. 106.1.1 |
| CITY AMENDMENTS TO FBC. |
| |
| 5- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE |
| EXTERIOR DOORS AND WINDOWS AS REQUIRED BY SEC. |
| R301.2.1.4.3 FLORIDA RESIDENTIAL CODE. |
| |
| 6- SPECIFY EGRESS FROM THE EXISTING BEDROOM AS REQUIRED |
| BY SEC. R310. |
| |
| 7- SPECIFY SMOKE ALARMS AS REQUIRED BY SEC. R313. |
| |
| 8- PROVIDE STRUCTURAL BUCK DETAILS FOR EXTERIOR DOORS |
| AND WINDOWS AS REQUIRED BY SEC. R613.6. |
| |
| 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. UPDATE THE VALUE TO INCLUDE ALL MATERIALS, LABOR |
| AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3 |
| CITY AMENDMENTS. |
| |
| 10- SHEET 1 OF 3 SUBMITTED: |
| A) INFORMATION ON FLOOR PLAN SUBMITTED IS NOT CLEAR. |
| (1) STEEL REINFORCING SPECIFICATIONS FOR CORNER COLUMNS |
| ARE NOT CLEAR AND DON'T MATCH INFORMATION SHOWN ON THE |
| FLOOR PLAN. (2) WHAT'S "NEW FRAME WALL LEADING TO BACK |
| OF HOUSE" NOTE MEANS. IS THIS FRAME ADDITION OR |
| CONCRETE BLOCK?. COORDINATE WITH WALL SECTION ON SHEET |
| 3 OF 3. (3) INFORMATION FOR NEW HALLWAY AND EXISTING |
| UTILITY IS NOT CLEAR. DRAWING DON'T SHOW THE WALLS AND |
| FRAMING AROUND DOORS IS NOT CLEAR. (4) SPECIFY VERTICAL |
| REINFORCEMENT AT THE ENDS OF DOORS AND WINDOWS |
| OPENINGS. |
| |
| B) REVISE GENERAL NOTES. (1) THERE IS NOT SBC. REFER TO |
| THE 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| (2) THERE IS NOT TABLE 1606.28. SEE 2007 FLORIDA |
| RESIDENTIAL L CODE AND SPECIFY ALL THE DESIGN LOADS AS |
| REQUIRED BY SEC. R301 AND TABLE R301.5. SPECIFY ALL THE |
| LIVE AND DEAD LOADS, BUILDING EXPOSURE AND THE WIND |
| SPEED. |
| |
| C) SPECIFY SIZE OF EXTERIOR DOORS AND WINDOWS TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSRUES OS SEC. |
| R301.2.1.4.3. |
| |
| 11- SHEET 3 OF 3: |
| A) REVISE WALL SECTIONS: (1) SPECIFY ALL STRUCTURAL |
| CONNECTORS. SEC. 106.1.2 CITY AMENDMENTS. (2) PROVIDE |
| ENGINEERING SHOWING REINFORCING FOR THE EXISTING ROOF |
| TRUSSES TO BE CUT. SEC. 106.1.2 CITY AMENDMENTS. (3) |
| COORDINATE VERTICAL REINFORCEMENT SHOWN ON THE TYPICAL |
| WALL SECTION WITH REVISED INFORMATION ON PLANS. |
| COORDINATE WITH ITEM #10(A) ABOVE. |
| |
| B) CLARIFY PLYWOOD NAILING NOTES. ARE THESE NOTES FOR |
| ROOF SHEATHING OR WALL SHEATHING. ROOF SHEATHING |
| REQUIRES MIN. 8D RING SHANK NAILS. SEE SEC. R803.2.3.1. |
| AND ROOF ZONE #3 REQUIRES NAIL SPACING AT 4"O.C. |
| |
| C) REVISE SPECIFICATIONS FOR EXISTING ROOF TILE. 30# |
| UNDERLAYMENT ALONE DOESN'T COMPLY WITH SEC. R905.3.3. |
| ALSO, CLARIFY IF PERMIT INCLUDES RE-ROOFING EXISTING |
| HOUSE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |