2012-01-19 09:17:15RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES
 ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF CHAPTER 13 FLORIDA RESIDENTIAL CODE.
  
 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOWS AS SHOWN ON PLANS.
  
 B) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 C) FLAT ROOF ASSEMBLY. AND, PLEASE SPECIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. ALSO,
 PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. NOTE: IF THE PRODUCT
 APPROVAL SUBMITTED REQUIRES SIGNED AND SEALED
 CALCULATIONS, THEN THOSE CALCULATIONS NEED TO BE SIGNED
 AND SEALED.
  
 D) HURRICANE SHUTTERS IF THE DOORS AND WINDOWS PRODUCT
 APPROVALS SUBMITTED DON'T HAVE IMPACT GLASS. AND,
 PROVIDE A COMPLETE SHUTTERS INSTALLATION SCHEDULE.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
  
 4- PROVIDE COMPLETE ROOF FRAMING PLAN. SHOW ALL FRAMING
 MEMBERS SIZES AND CONNECTORS. SPECIFY ATTACHMENT TO
 EXISTING ROOF. SPECIFY ROOF SLOPE. ETC. SEC. 106.1.1
 CITY AMENDMENTS TO FBC.
  
 5- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS AS REQUIRED BY SEC.
 R301.2.1.4.3 FLORIDA RESIDENTIAL CODE.
  
 6- SPECIFY EGRESS FROM THE EXISTING BEDROOM AS REQUIRED
 BY SEC. R310.
  
 7- SPECIFY SMOKE ALARMS AS REQUIRED BY SEC. R313.
  
 8- PROVIDE STRUCTURAL BUCK DETAILS FOR EXTERIOR DOORS
 AND WINDOWS AS REQUIRED BY SEC. R613.6.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE THE VALUE TO INCLUDE ALL MATERIALS, LABOR
 AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3
 CITY AMENDMENTS.
  
 10- SHEET 1 OF 3 SUBMITTED:
 A) INFORMATION ON FLOOR PLAN SUBMITTED IS NOT CLEAR.
 (1) STEEL REINFORCING SPECIFICATIONS FOR CORNER COLUMNS
 ARE NOT CLEAR AND DON'T MATCH INFORMATION SHOWN ON THE
 FLOOR PLAN. (2) WHAT'S "NEW FRAME WALL LEADING TO BACK
 OF HOUSE" NOTE MEANS. IS THIS FRAME ADDITION OR
 CONCRETE BLOCK?. COORDINATE WITH WALL SECTION ON SHEET
 3 OF 3. (3) INFORMATION FOR NEW HALLWAY AND EXISTING
 UTILITY IS NOT CLEAR. DRAWING DON'T SHOW THE WALLS AND
 FRAMING AROUND DOORS IS NOT CLEAR. (4) SPECIFY VERTICAL
 REINFORCEMENT AT THE ENDS OF DOORS AND WINDOWS
 OPENINGS.
  
 B) REVISE GENERAL NOTES. (1) THERE IS NOT SBC. REFER TO
 THE 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
 (2) THERE IS NOT TABLE 1606.28. SEE 2007 FLORIDA
 RESIDENTIAL L CODE AND SPECIFY ALL THE DESIGN LOADS AS
 REQUIRED BY SEC. R301 AND TABLE R301.5. SPECIFY ALL THE
 LIVE AND DEAD LOADS, BUILDING EXPOSURE AND THE WIND
 SPEED.
  
 C) SPECIFY SIZE OF EXTERIOR DOORS AND WINDOWS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSRUES OS SEC.
 R301.2.1.4.3.
  
 11- SHEET 3 OF 3:
 A) REVISE WALL SECTIONS: (1) SPECIFY ALL STRUCTURAL
 CONNECTORS. SEC. 106.1.2 CITY AMENDMENTS. (2) PROVIDE
 ENGINEERING SHOWING REINFORCING FOR THE EXISTING ROOF
 TRUSSES TO BE CUT. SEC. 106.1.2 CITY AMENDMENTS. (3)
 COORDINATE VERTICAL REINFORCEMENT SHOWN ON THE TYPICAL
 WALL SECTION WITH REVISED INFORMATION ON PLANS.
 COORDINATE WITH ITEM #10(A) ABOVE.
  
 B) CLARIFY PLYWOOD NAILING NOTES. ARE THESE NOTES FOR
 ROOF SHEATHING OR WALL SHEATHING. ROOF SHEATHING
 REQUIRES MIN. 8D RING SHANK NAILS. SEE SEC. R803.2.3.1.
 AND ROOF ZONE #3 REQUIRES NAIL SPACING AT 4"O.C.
  
 C) REVISE SPECIFICATIONS FOR EXISTING ROOF TILE. 30#
 UNDERLAYMENT ALONE DOESN'T COMPLY WITH SEC. R905.3.3.
 ALSO, CLARIFY IF PERMIT INCLUDES RE-ROOFING EXISTING
 HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712