2012-02-07 19:10:31PLEASE RESPOND TO COMMENTS IN WRITING:
  
 SHEET C3-2 "GATES AND WALL SECTIONS"
 THE SECTION NUMBER ON EACH SECTION TITLE SHOULD REFLECT
 THE SHEET NUMBER WHERE
 SECTION WAS TAKEN FROM. HAVING SAID THIS, THE CALL OUT
 OF C3-2 ON EACH SECTION TITLE
 SHOULD BE SHOULD BE C3-1.
 (NOTE: SEE AS AN EXAMPLE, THE STRUCTURAL SHEETS, THOSE
 WHERE DONE CORRECTLY)
  
 SHEET C5-1 "CIVIL DETAILS"
 THE SECTION NUMBER ON EACH SECTION TITLE SHOULD REFLECT
 THE SHEET NUMBER WHERE
 SECTION WAS TAKEN FROM. HAVING SAID THIS, THE CALL OUT
 OF C5-1 ON EACH SECTION TITLE
 SHOULD BE SHOULD BE REFERENCED TO C1-2 AND C1-3.
 (NOTE: SEE AS AN EXAMPLE, THE STRUCTURAL SHEETS, THOSE
 WHERE DONE CORRECTLY)
  
 SHEET C3-1 "DIVIDE STRUCTURE SECTIONS"
 THIS SHEET SHOWS ON DETAIL 1 A GATE OPENING OF 11' HIGH
 (SHOWN AS 11' OPENING)
 SHEET C3-2 ON SECTION OR DETAIL 6 "MULTIPLE DISC SLIDE
 GATE NO. 2 FULLY RAISED" SHOWS
 A CLEAR OPENING OF 6' AND NOT 11' ON SECTION OR DETAIL
 4 IT SHOWS 9'.
 IT SEEMS A LITTLE CONFUSING WITHOUT A BETTER
 DESCRIPTION FOR EACH MODE OF OPERATION OF THE DISKS.
  