2012-01-06 11:32:2111120506
 771 N AUSTRALIAN AVE
 WPB PUMP STATION
  
 GROUND-FAULT PROTECTION OF EQUIPMENT (GFPE) IS REQUIRED
 FOR THE SERVICE. NEC 230.95
 PROVIDE A LABELING SCHEDULE FOR THE WARNING AND SAFETY
 SIGNAGE REQUIRED FOR THE ELECTRICAL EQUIPMENT. NEC
 110.22, 110.16, 701.9
 INDICATE THE SIZE OF THE PORTABLE GENERATOR FEEDERS TO
 THE TRANSFER SWITCH. NEC 450.13
 HOW IS THE LOAD ON THE PORTABLE GENERATOR TO BE
 MANAGED? NEC 702.5
 THE SIZE OF THE MAIN BREAKER FOR PANEL BOARDS ?A? AND
 ?B? HAS NOT BEEN SPECIFIED.
 THE FAULT CURRENT CAPABILITY FOR THE THREE 100 AMP
 PANELS HAS NOT BEEN SPECIFIED.
  