2011-12-29 14:43:346501 NORTH JOG ROAD
 PERMIT #11120483
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WATER MAINS AND FIRE HYDRANTS SHALL BE INSTALLED,
 TESTED AND APPROVED PRIOR TO COMMENCING CONSTRUCTION
 WORK ON ANY STRUCTURE.
  
 INDICATE WHAT FLOW AND PRESSURE IS ANTICIPATED TO BE
 AVAILABLE AT THESE HYDRANTS.
  
 AFTER THE MASTER METER, SEPARATE THE FIRE MAIN SO IT IS
 INDEPENDENT OF THE DOMESTIC WATER SERVICE. PROVIDE AN
 INDICATING VALVE (PIV OR BACKFLOW PREVENTER) FOR THE
 FIRE MAIN. INDICATING VALVE(S) SHALL BE SUPERVISED IN
 THE OPEN POSITION.
  
 PER NFPA 24, SECTION 8.7 PROHIBITS USING FIRE HYDRANTS
 FOR PURPOSES OTHER THAN FIRE-RELATED SERVICES.
  
 ON THE EAST SIDE OF JOG ROAD THE PLANS INDICATE
 ADDITIONAL STORAGE AND TRAILERS, INDICATE THE WATER
 SUPPLY AND FIRE HYDRANTS THAT WILL BE PROTECTING THIS
 AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  