2012-02-13 15:40:20BUILDING PLAN REVIEW
 PERMIT: 11120482
 ADD: 6501 N JOG RD
 CONT: D. S. EAKINS CONSTRUCTION CORP
 TEL: (561)719-6669
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
  
  
 BUILDING PROVISO:
  
 NOTE: APA ENGINEERED WOOD SYSTEMS BULLETIN OCT. 1995
 120 MPH FASTEST MILE = 140 MPH 3 SECOND GUST
  
 2007/09 FBC-B 1609.1.2.
 EXCEPTION # 1)
 WOOD STRUCTURAL PANELS WITH A MINIMUM THICKNESS OF 7/16
 INCH (11.1 MM) AND A MAXIMUM SPAN OF 8 FEET (2438 MM)
 SHALL BE PERMITTED FOR OPENING PROTECTION IN ONE- AND
 TWO-STORY BUILDINGS. PANELS SHALL BE PRECUT SO THAT
 THEY SHALL BE ATTACHED TO THE FRAMING SURROUNDING THE
 OPENING CONTAINING THE PRODUCT WITH THE GLAZED
 OPENINGS. PANELS SHALL BE PREDRILLED AS REQUIRED FOR
 THE ANCHORAGE METHOD AND ALL REQUIRED HARDWARE SHALL BE
 PROVIDED. ATTACHMENT SHALL BE DESIGNED TO RESIST THE
 COMPONENTS AND CLADDING LOADS DETERMINED IN ACCORDANCE
 WITH THE PROVISIONS OF ASCE 7, WITH PERMANENT
 CORROSION-RESISTANT ATTACHMENT HARDWARE PROVIDED AND
 ANCHORS PERMANENTLY INSTALLED ON THE BUILDING.
 ATTACHMENT IN ACCORDANCE WITH TABLE 1609.1.2, WITH
 PERMANENT CORROSION RESISTANT ATTACHMENT HARDWARE
 PROVIDED AND ANCHORS PERMANENTLY INSTALLED ON THE
 BUILDING IS PERMITTED FOR BUILDINGS WITH A MEAN ROOF
 HEIGHT OF 45 FEET (13 716 MM) OR LESS WHERE WIND SPEEDS
 DO NOT EXCEED 140 MPH (63 M/S)
  