| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SITE COMMENTS |
| |
| ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. |
| |
| PER NFPA 241 - TABLE 4.2.1 (2009 ED.), THE CONSTRUCTION |
| TRAILERS SHALL BE SEPARATED FROM EACH OTHER BY A |
| DISTANCE OF 30'-60' DEPENDING UPON THE EXPOSING WALL |
| LENGTHS. NOTE: SEPARATION DISTANCES CAN BE REDUCED BY |
| 75% WHEN THE STRUCTURES ARE FULLY SPRINKLERED. |
| |
| IDENTIFY EACH TRAILER WITH AN ADDRESS OR UNIT |
| LETTER/NUMBER. CHARACTERS SHALL BE ATTACHED TO THE |
| BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH |
| 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. |
| |
| ALL GATES WILL NEED TO BE PROVIDED WITH KNOX KEY |
| SWITCHES OR KNOX PADLOCKS TO ALLOW ACCESS TO EMERGENCY |
| RESPONDERS. KEY SWITCHES AND PADLOCKS CAN BE ORDERED |
| FROM WWW.KNOXBOX.COM. |
| |
| THE EMERGENCY VEHICLE ACCESS LANE NEAR THE TRAILERS |
| SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE |
| LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT" |
| SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND |
| RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN |
| HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN |
| SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 |
| FEET APART. |
| |
| POST WEATHERPROOF NO SMOKING SIGNS ON ALL CONSTRUCTION |
| TRAILERS. SMOKING SHALL BE PERMITTED ONLY DESIGNATED |
| AREAS. PROVIDE SAFE RECEPTACLES FOR DISCARDED SMOKING |
| MATERIALS. |
| |
| ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS SHALL BE |
| PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE |
| PROJECT AND MAINTAINED UNTIL COMPLETION. |
| |
| WET FIRE HYDRANTS SHALL BE INSTALLED, TESTED AND |
| INSPECTED PRIOR TO THE START OF ANY CONSTRUCTION |
| ACTIVITIES. |
| |
| A SUITABLE LOCATION AT THE SITE SHALL BE DESIGNATED AS |
| A COMMAND POST AND PROVIDED WITH PLANS, EMERGENCY |
| INFORMATION, KEYS, COMMUNICATIONS, AND EQUIPMENT, AS |
| NEEDED. |
| |
| CONSTRUCTION TRAILER COMMENTS |
| |
| NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| |
| IN ADDITION TO THE FLORIDA BUILDING CODE, THE FIRE |
| PROTECTION AND LIFE SAFETY DESIGN SHALL CONFORM TO THE |
| 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE (2009 |
| EDITION OF NFPA 1 & NFPA 101 WITH FLORIDA AMENDMENTS). |
| |
| INDICATE THE LOCATIONS OF ALL STAIRS THAT EGRESS THE |
| PLATFORM CONNECTING ALL THE TRAILERS. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS WITH EXIT |
| SIGNS. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| INDICATE IF THERE ARE ANY CONFERENCE OR MEETING ROOMS |
| THAT WILL BE TREATED AS AN ASSEMBLY OCCUPANCY |
| ACCOMPANYING 50 OR MORE PERSONS. |
| |
| SHEET A1 DOES NOT BEAR THE SIGNATURE/SEAL OF THE DESIGN |
| PROFESSIONAL. |
| |
| NOTE: THE CONSTRUCTION TRAILERS WILL BE TREATED AS |
| PERMANENT STRUCTURES AS THEY WILL REMAIN IN PLACE FOR |
| MORE THAN 180 DAYS. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |