Plan Review Notes
Plan Review Notes For Permit 11120482
Permit Number 11120482
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-12-29 15:44:456501 NORTH JOG ROAD
 PERMIT #11120482
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SITE COMMENTS
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 PER NFPA 241 - TABLE 4.2.1 (2009 ED.), THE CONSTRUCTION
 TRAILERS SHALL BE SEPARATED FROM EACH OTHER BY A
 DISTANCE OF 30'-60' DEPENDING UPON THE EXPOSING WALL
 LENGTHS. NOTE: SEPARATION DISTANCES CAN BE REDUCED BY
 75% WHEN THE STRUCTURES ARE FULLY SPRINKLERED.
  
 IDENTIFY EACH TRAILER WITH AN ADDRESS OR UNIT
 LETTER/NUMBER. CHARACTERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 ALL GATES WILL NEED TO BE PROVIDED WITH KNOX KEY
 SWITCHES OR KNOX PADLOCKS TO ALLOW ACCESS TO EMERGENCY
 RESPONDERS. KEY SWITCHES AND PADLOCKS CAN BE ORDERED
 FROM WWW.KNOXBOX.COM.
  
 THE EMERGENCY VEHICLE ACCESS LANE NEAR THE TRAILERS
 SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE
 LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT"
 SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND
 RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN
 HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN
 SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60
 FEET APART.
  
 POST WEATHERPROOF NO SMOKING SIGNS ON ALL CONSTRUCTION
 TRAILERS. SMOKING SHALL BE PERMITTED ONLY DESIGNATED
 AREAS. PROVIDE SAFE RECEPTACLES FOR DISCARDED SMOKING
 MATERIALS.
  
 ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS SHALL BE
 PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE
 PROJECT AND MAINTAINED UNTIL COMPLETION.
  
 WET FIRE HYDRANTS SHALL BE INSTALLED, TESTED AND
 INSPECTED PRIOR TO THE START OF ANY CONSTRUCTION
 ACTIVITIES.
  
 A SUITABLE LOCATION AT THE SITE SHALL BE DESIGNATED AS
 A COMMAND POST AND PROVIDED WITH PLANS, EMERGENCY
 INFORMATION, KEYS, COMMUNICATIONS, AND EQUIPMENT, AS
 NEEDED.
  
 CONSTRUCTION TRAILER COMMENTS
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 IN ADDITION TO THE FLORIDA BUILDING CODE, THE FIRE
 PROTECTION AND LIFE SAFETY DESIGN SHALL CONFORM TO THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE (2009
 EDITION OF NFPA 1 & NFPA 101 WITH FLORIDA AMENDMENTS).
  
 INDICATE THE LOCATIONS OF ALL STAIRS THAT EGRESS THE
 PLATFORM CONNECTING ALL THE TRAILERS.
  
 PROVIDE TACTILE SIGNAGE AT ALL EXIT DOORS WITH EXIT
 SIGNS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 INDICATE IF THERE ARE ANY CONFERENCE OR MEETING ROOMS
 THAT WILL BE TREATED AS AN ASSEMBLY OCCUPANCY
 ACCOMPANYING 50 OR MORE PERSONS.
  
 SHEET A1 DOES NOT BEAR THE SIGNATURE/SEAL OF THE DESIGN
 PROFESSIONAL.
  
 NOTE: THE CONSTRUCTION TRAILERS WILL BE TREATED AS
 PERMANENT STRUCTURES AS THEY WILL REMAIN IN PLACE FOR
 MORE THAN 180 DAYS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  