2012-01-04 16:48:08 | BUILDING PLAN REVIEW |
| PERMIT: 11120482 |
| ADD: 6501 N JOG RD |
| CONT: D. S. EAKINS CONSTRUCTION CORP |
| TEL: (561)719-6669 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) DISCREPANCY BETWEEN THE STATE APPROVED SOUTHEAST |
| MODULAR MANUFACTURING PLAN (SHEET 2 OF 6) WITH 3920 SQ |
| FT AND THE COPIED NOT SEALED FOUNDATION PLAN FROM |
| WILLIAM SCOTSMAN PLAN (SHEET 4) FOR 2880 SQ FT. PLEASE |
| PROVIDE THE FOUNDATION PLAN THAT MATCHES TO THE |
| SOUTHEAST MANUFACTURING PLAN. NOTE THIS IS A SITE |
| SPECIFIC ENGINEERING WITCH WILL REQUIRE A ENGINEER SEAL |
| AND SIGNATURE. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| |
| 2) SHEET A1 RAMP DETAILS IS ALSO NOT SIGNED NOR SEALED |
| BY THE DESIGN PROFESSIONAL. PLEASE NOTE THE SHEET A1 IS |
| FOR A STRAIGHT RUN RAMP DETAIL WHILE THE STAGING PLAN |
| FROM BE & K # 700-C0-020 INDICATES A RAMP WITH A SWITCH |
| BACK AND A MID LANDING, PLEASE PROVIDE AN ENGINEERED |
| PLAN THAT FITS THIS INSTALATION APPLICATION. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| |
| 3) THE PERMIT APPLICATION INDICATES THAT THE |
| INSTALATION OF CONSTRUCTION TRAILERS ARE THESE ACTUALLY |
| TRAILERS? ARE THEY GOING TO HAVE STORAGE OF |
| CONSTRUCTION MATERIALS? OR ARE THEY MANUFACTURED |
| BUILDING THAT WILL BE BROUGHT IN ARE FOR BUSINESS USAGE |
| TO BE USED FOR THE ADMINISTRATION OF THE PROJECT? THE |
| STATE APPROVED PLANS INDICATES THEY |
| WERE BUILT WITH THE INTENT OF BUSINESS OFFICES. THIS |
| REVIEW WILL BE WITH THE INTENDED USE AS APPROVED BY THE |
| STATE, BUSINESS OCCUPANCY. |
| |
| 3A) THE DESIGNER OF RECORD WILL NEED TO CLARIFY IF EACH |
| UNIT IS TO BE CONSIDERED A SINGLE BUILDING OF 3920 SQ |
| FT OR IF MULTIPLE UNITS TWO OR MORE BUILDINGS ARE GOING |
| TO BE CONSIDERED A SINGLE UNIT. PLEASE REVIEW FBC-B |
| TABLE 503 FOR A BUSINESS OCCUPANCY A TYPE V-B ALLOWS AN |
| AREA OF 9,000 SQ FT THESE UNITS ARE NOT FIRE |
| SPRINKLERED NO INCREASE CAN BE TAKEN FOR FIRE |
| SPRINKLERS BUT DEPENDING ON THE CONFIGURATION, FRONTAGE |
| INCREASES MAY BE TAKEN FBC-B 506.2 WHICH WOULD CREATE A |
| LARGER BUILDING. |
| |
| 3B) PLEASE REVIEW TABLE 502 FOR FIRE RESISTANCE RATING |
| REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| SEPERATION DISTANCE. THE STATE APPROVED PLANS INDICATES |
| THAT THERE IS NO FIRE RATING OF THE EXTERIOR WALLS. FOR |
| A TYPE V-B BUILDING THE MINIMUM DISTANCE FROM AN |
| ASSUMED PROPERTY LINE WOULD BE 10 FEET TO AN ASSUMED |
| PROPERTY LINE OR 20 FEET FROM ONE BUILDING TO ANOTHER. |
| THE SITE PLAN INDICATES AN AREA WHERE TWO MORE UNITS |
| MAY BE BROUGHT IN, THIS MAY NEED TO BE ADDRESSED AT |
| THIS TIME AS FAR AS THE SQUARE FOOTAGE THAT WOULD BE |
| ALLOWED AND THE ASSUMED PROPERTY LINE BETWEEN UNITS. |
| THE 2007 FBC-B CODE COMMENTARY FIGURE 602A HAS MORE |
| INFORMATION ON ASSUMED PROPERTY LINES. |
| |
| 4) PLEASE NOTE THAT SHEET 4 IS THE WRONG FOUNDATION |
| PLAN THE REQUIREMENT FOR FOUNDATIONS IS OUT OF THE |
| 2007/09 FBC-B AND THE REQUIREMENTS FOR DEPTH OF |
| FOUNDATIONS |
| 1805.2 IS STILL A MINIMUM OF 12 INCHES BELOW GRADE. |
| PLEASE ALSO REVIEW 1805.5.7 FOR PIER FOUNDATIONS AND |
| WIND SPEED. |
| |
| 5) PLEASE REVIEW SHEET # 1 OF SITE INSTALLED ITEMS |
| PORTABLE FIRE EXTINGUISHERS, STORM SHUTTERS, GUTTERS & |
| DOWN SPOUTS AND DRINKING FOUNTAINS. |
| |
| 6) STAGING PLAN DOES NOT PROVIDE DETAIL FOR THE |
| HANDICAPPED PARKING AND ACCESS AILSE FBC11-4.6.2(1) & |
| 11-4.6.4. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |