2012-05-08 09:12:10NEW PLANS DO NOT MATCH PREVIOUSLY REVIEWED PLANS.
 PLEASE PROVIDE THE FOLLOWING.
  
 11120372
 437 8TH ST.
 REMODEL
  
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 SHOW SERVICE RISER PLAN AND LOCATION OF SERVICE. NEC
 215.15
 ADD RECEPTACLES IN THE KITCHEN, FOR THE COUNTER TOP AND
 THE ADJOINING ROOM OF THE SECOND FLOOR UNIT. NEC 210.52
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE ELECTRICAL
 SERVICE. NEC 250.94
  