Plan Review Notes
Plan Review Notes For Permit 11120372
Permit Number 11120372
Review Stop B
Sequence Number 3
Notes
Date Text
2012-04-13 16:42:42RESIDENTIAL ALTERATION BUILDING REVIEW THIRD CHECKLIST.
  
 1- ENGINEER NEEDS TO SIGN AND SEAL BOTH SETS OF PLANS
 AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. ONLY ONE
 SET WAS SIGNED AND SEALED.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM
 ALSO.
  
 3- ORIGINAL COMMENT: PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE TENANT
 SEPARATION REQUIREMENTS OF SEC. R317.1. SPECIFY UL FIRE
 RATED ASSEMBLY OR ANY OTHER APPROVED ASSEMBLY. ANY
 PENETRATIONS NEED TO BE RATED AS REQUIRED BY SEC.
 R317.3.
 PLANS SUBMITTED DON'T SPECIFY ANY TESTED AND APPROVED
 ASSEMBLY. ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE
 WITH ASTM E 119. AND, FIRE-RESISTANCE-RATED
 FLOOR-CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL AS REQUIRED BY SEC.
 R317.1. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE. PLEASE SPECIFY ANY UL OR DRYWALL
 APPROVED AND LISTED ASSEMBLY.
  
 ENGINEER'S RESPONSE: UL ASSEMBLY U-419 AND GYPSUM
 ASSOCIATION ASSEMBLY WP1200 ARE FOR INTERIOR
 NON-BEARING PARTITIONS USING STEEL STUDS. THIS IS NOT
 THE TYPE OF CONSTRUCTION FOR THIS BUILDING. PROVIDE
 COMPLETE AND CORRECT SPECIFICATIONS FOR TYPE OF
 CONSTRUCTION IN THIS BUILDING.
  
 ***NOTE: ENGINEER TO REVIEW FLORIDA STATUTE
 553.80(2)(B) REGARDING DESIGN PROFESSIONAL DOCUMENTS. A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW SHALL BE
 CHARGED TO THE ENGINEER EACH TIME AFTER THE THIRD
 REVIEW IS REJECTED FOR THE SAME COMMENT.
  
 4- ORIGINAL COMMENT: PROVIDE COMPLETE INFORMATION FOR
 STAIRWAY HANDRAILS AND GUARDRAILS TO SHOW COMPLIANCE
 WITH SEC. R311.5.6 THRU SEC. R311.5.6.3 AND SEC. R312.
 IN ADDITION THE GUARDRAIL AND HANDRAIL NEED TO COMPLY
 WITH THE DESIGN LOADS OF TABLE R301.5. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS. ALSO, NEED TO PROVIDE
 FRAMING DETAILS FOR STAIRS TOP LANDING. ALSO, SPECIFY
 COMPLIANCE WITH THE STAIR CONSTRUCTION AS REQUIRED BY
 SEC. R311.2.
  
 A) PLANS SUBMITTED DON'T PROVIDE ANY DETAILS/
 SPECIFICATIONS FOR THE HANDRAIL AND GUARDRAIL
 CONSTRUCTION SHOWING COMPLIANCE WITH THE LOADS OF TABLE
 R301.5.
 B) GUARDRAIL HEIGHT IS NOT GIVEN. SEC. R311.5.6.1 AND
 SEC. R312.1.
 C) HOW IS THE 2X TOP LANDING LEDGER ATTACHED TO
 EXISTING WALL?. INFORMATION GIVEN IS NOT CLEAR AND IT
 DOESN'T MENTION ATTACHMENT OF THE LEDGER TO THE WALL.
 D) HOW ARE THE 3-2X12 STRINGERS ATTACHED TO THE BASE?.
 SIMPSON LU28 HANGER SPECIFIED CAN'T BE BENT DOWN TO
 RECEIVE THE STRINGER. NEED TO SPECIFY CORRECT CONNECTOR
 THAT IS DESIGNED TO RECEIVED SLOPED STRINGER.
  
 5- ORIGINAL COMMENT: PROVIDE PRODUCT APPROVAL (2
 COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NO PRODUCT APPROVALS SUBMITTED. PROVIDE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC
 CONNECTOR ONLY.
  
 6- SHEET #1:
 A) ORIGINAL COMMENT. REVISE TENANT SEPARATION WALL
 SECTION TO COMPLY WITH ITEM #3 ABOVE. AND, COORDINATE
 WITH INFORMATION SHOWN ON THE 2 STORY WALL SECTION.
 NEED TO COORDINATE INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712