Date |
Text |
2012-04-13 16:42:42 | RESIDENTIAL ALTERATION BUILDING REVIEW THIRD CHECKLIST. |
| |
| 1- ENGINEER NEEDS TO SIGN AND SEAL BOTH SETS OF PLANS |
| AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. ONLY ONE |
| SET WAS SIGNED AND SEALED. |
| |
| 2- ENERGY CALCULATIONS SUBMITTED: |
| A) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM |
| ALSO. |
| |
| 3- ORIGINAL COMMENT: PROVIDE COMPLETE DRAWINGS AND |
| SPECIFICATIONS SHOWING COMPLIANCE WITH THE TENANT |
| SEPARATION REQUIREMENTS OF SEC. R317.1. SPECIFY UL FIRE |
| RATED ASSEMBLY OR ANY OTHER APPROVED ASSEMBLY. ANY |
| PENETRATIONS NEED TO BE RATED AS REQUIRED BY SEC. |
| R317.3. |
| PLANS SUBMITTED DON'T SPECIFY ANY TESTED AND APPROVED |
| ASSEMBLY. ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE |
| WITH ASTM E 119. AND, FIRE-RESISTANCE-RATED |
| FLOOR-CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND |
| BE TIGHT AGAINST THE EXTERIOR WALL AS REQUIRED BY SEC. |
| R317.1. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| SHOWING COMPLIANCE. PLEASE SPECIFY ANY UL OR DRYWALL |
| APPROVED AND LISTED ASSEMBLY. |
| |
| ENGINEER'S RESPONSE: UL ASSEMBLY U-419 AND GYPSUM |
| ASSOCIATION ASSEMBLY WP1200 ARE FOR INTERIOR |
| NON-BEARING PARTITIONS USING STEEL STUDS. THIS IS NOT |
| THE TYPE OF CONSTRUCTION FOR THIS BUILDING. PROVIDE |
| COMPLETE AND CORRECT SPECIFICATIONS FOR TYPE OF |
| CONSTRUCTION IN THIS BUILDING. |
| |
| ***NOTE: ENGINEER TO REVIEW FLORIDA STATUTE |
| 553.80(2)(B) REGARDING DESIGN PROFESSIONAL DOCUMENTS. A |
| FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW SHALL BE |
| CHARGED TO THE ENGINEER EACH TIME AFTER THE THIRD |
| REVIEW IS REJECTED FOR THE SAME COMMENT. |
| |
| 4- ORIGINAL COMMENT: PROVIDE COMPLETE INFORMATION FOR |
| STAIRWAY HANDRAILS AND GUARDRAILS TO SHOW COMPLIANCE |
| WITH SEC. R311.5.6 THRU SEC. R311.5.6.3 AND SEC. R312. |
| IN ADDITION THE GUARDRAIL AND HANDRAIL NEED TO COMPLY |
| WITH THE DESIGN LOADS OF TABLE R301.5. PROVIDE COMPLETE |
| DETAILS AND SPECIFICATIONS. ALSO, NEED TO PROVIDE |
| FRAMING DETAILS FOR STAIRS TOP LANDING. ALSO, SPECIFY |
| COMPLIANCE WITH THE STAIR CONSTRUCTION AS REQUIRED BY |
| SEC. R311.2. |
| |
| A) PLANS SUBMITTED DON'T PROVIDE ANY DETAILS/ |
| SPECIFICATIONS FOR THE HANDRAIL AND GUARDRAIL |
| CONSTRUCTION SHOWING COMPLIANCE WITH THE LOADS OF TABLE |
| R301.5. |
| B) GUARDRAIL HEIGHT IS NOT GIVEN. SEC. R311.5.6.1 AND |
| SEC. R312.1. |
| C) HOW IS THE 2X TOP LANDING LEDGER ATTACHED TO |
| EXISTING WALL?. INFORMATION GIVEN IS NOT CLEAR AND IT |
| DOESN'T MENTION ATTACHMENT OF THE LEDGER TO THE WALL. |
| D) HOW ARE THE 3-2X12 STRINGERS ATTACHED TO THE BASE?. |
| SIMPSON LU28 HANGER SPECIFIED CAN'T BE BENT DOWN TO |
| RECEIVE THE STRINGER. NEED TO SPECIFY CORRECT CONNECTOR |
| THAT IS DESIGNED TO RECEIVED SLOPED STRINGER. |
| |
| 5- ORIGINAL COMMENT: PROVIDE PRODUCT APPROVAL (2 |
| COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR: |
| A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. |
| NO PRODUCT APPROVALS SUBMITTED. PROVIDE PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC |
| CONNECTOR ONLY. |
| |
| 6- SHEET #1: |
| A) ORIGINAL COMMENT. REVISE TENANT SEPARATION WALL |
| SECTION TO COMPLY WITH ITEM #3 ABOVE. AND, COORDINATE |
| WITH INFORMATION SHOWN ON THE 2 STORY WALL SECTION. |
| NEED TO COORDINATE INFORMATION. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |