Plan Review Notes For Permit 11120372 |
Permit Number |
11120372 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-02-29 15:41:11 | 11120372 | | 437 8TH ST. | | REMODEL | | | | ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED | | WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | PROVIDE AN AS BUILT ELECTRIC SERVICE RISER PLAN FOR THE | | BUILDING. INDICATE THE LOCATION OF THE SERVICE AND ALL | | SERVICE DISCONNECTS FOR ALL UNITS. NEC 215.15 | | ADD RECEPTACLES IN THE KITCHEN. NEC 201.52 | | CLARIFY THE USE OF THE FIRST FLOOR STUDIO. IS IT AN | | APARTMENT OR STORAGE? | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|