2012-02-29 15:41:1111120372
 437 8TH ST.
 REMODEL
  
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 PROVIDE AN AS BUILT ELECTRIC SERVICE RISER PLAN FOR THE
 BUILDING. INDICATE THE LOCATION OF THE SERVICE AND ALL
 SERVICE DISCONNECTS FOR ALL UNITS. NEC 215.15
 ADD RECEPTACLES IN THE KITCHEN. NEC 201.52
 CLARIFY THE USE OF THE FIRST FLOOR STUDIO. IS IT AN
 APARTMENT OR STORAGE?
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER