Plan Review Notes For Permit 11120372 |
Permit Number |
11120372 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-09 16:40:31 | 11120372 | | 437 8TH ST. | | REMODEL | | | | ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC | | FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED | | OUTSIDE FRONT AND BACK. NEC 210.70 | | PROVIDE AN EXTERIOR LIGHT FOR THE TOP UNIT. NEC 210.70 | | SHOW SERVICE RISER PLAN AND LOCATION OF SERVICE. NEC | | 215.15 | | ADD RECEPTACLES IN THE KITCHEN AND THE ADJOINING ROOM | | OF THE SECOND FLOOR UNIT. NEC 201.52 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | | | |
|