 437 8TH ST.
 REMODEL
  
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.70
 PROVIDE AN EXTERIOR LIGHT FOR THE TOP UNIT. NEC 210.70
 SHOW SERVICE RISER PLAN AND LOCATION OF SERVICE. NEC
 215.15
 ADD RECEPTACLES IN THE KITCHEN AND THE ADJOINING ROOM
 OF THE SECOND FLOOR UNIT. NEC 201.52
  