Plan Review Notes For Permit 11120366
Permit Number 11120366
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-09 16:05:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE ENGINEERING WHICH SHOWS HOW PROPOSED
 GENERATOR WILL RESIST WIND LOADS, FBC1609. THE
 MANUFACTURER'S INTALLATION INSTRUCTIONS DO NOT INCLUDE
 A WIND DESING CRITERIA (140MPH, EXPOSURE C MINIMUM).
  