Plan Review Notes For Permit 11120277 |
Permit Number |
11120277 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-16 13:53:06 | 1507 BELVEDERE ROAD | | PERMIT #11120277 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | INDICATE DUCT SMOKE DETECTOR LOCATIONS. | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED AND | | IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|