Plan Review Notes
Plan Review Notes For Permit 11120195
Permit Number 11120195
Review Stop B
Sequence Number 3
Notes
Date Text
2012-04-09 13:32:39BUILDING PLAN REVIEW
 PERMIT: 11120195
 ADD: 8264 NORTHLAKE BLVD
 CONT: TO BE DETERMINED
 TEL: (561)805-6700 SAM DORFMAN
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 APRIL 09/2012
 ACTION: DENIED
 2007/09 EXISTING BUILDING CODE:
 1001.1 SCOPE. AN ADDITION TO A BUILDING OR STRUCTURE
 SHALL COMPLY WITH THE FLORIDA BUILDING CODE AS ADOPTED
 FOR NEW CONSTRUCTION WITHOUT REQUIRING THE EXISTING
 BUILDING OR STRUCTURE TO COMPLY WITH ANY REQUIREMENTS
 OF THOSE CODES OR OF THESE PROVISIONS, EXCEPT AS
 REQUIRED BY THIS CHAPTER. WHERE AN ADDITION IMPACTS THE
 EXISTING BUILDING OR STRUCTURE, THAT PORTION SHALL
 COMPLY WITH THIS CODE.
  
 1001.2 CREATION OR EXTENSION OF NONCONFORMITY. AN
 ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY
 IN THE EXISTING BUILDING TO WHICH THE ADDITION IS BEING
 MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH,
 FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF
 MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
  
 1A) SHEET D1.0 NOTES D1-3 INDICATE THE REUSE OF
 ANDERSON WOOD WINDOWS AND DOORS. THIS BUILDING (PERMIT
 # 94013940) WAS BUILT UNDER THE 1991 SBCCI AND THE WIND
 SPEED WAS 110 MPH FASTEST MILE THAT CONVERTS OVER TO
 130 MPH 3 SECOND GUST UNDERTHE 2007/ 09 FBC-B. HOW WILL
 YOU DEMONSTRATE CODE COMPLIANCE FOR WIND FOR THE
 ANDERSON WINDOWS AND DOORS? 2007/09 FBC-B 1609
 COMPONENTS & CLADDING FOR WIND PRESSURES?
 RESPONSE INDICATES THE USE OF STORM PANEL SYSTEM TO
 MEET THE DIFFERENCE IN WIND PRESSURES BETWEEN THE 1991
 SBCCI 110 MPH WHICH EQUALS 130MPH 3 SECOND GUST WHICH
 OUR CURRENT CODE USES TO MEASURE WIND PRESSURE. THE
 CITY OF WEST PALM BEACH IS LOCATE IN A 140 MPH 3 SECOND
 GUSST WIND ZONE. THE STORM SHUTTERS WIL NOT HELP WITH
 WIND PRESSURE SINCE SHUTTERS ARE PERMIABLE, ALLOW TO
 FLOW THROUGH. PLEASE REVIEW COMMENTS ABOUT SCOPING
 EXISTING BUILDING CODE 1001.2 AND LEVEL II ALTERATIONS
 ALL NEW ELEMENTS MUST MEET THE REQUIREMENTS FOR NEW
 CONSTRUCTION!!!!
  
 EXISTING BUILDING CODE 1003.3.2 HORIZONTAL ADDITION.
 WHERE HORIZONTAL ADDITIONS ARE STRUCTURALLY CONNECTED
 TO AN EXISTING STRUCTURE, ALL LATERAL-FORCE-RESISTING
 ELEMENTS OF THE EXISTING STRUCTURE AFFECTED BY SUCH
 ADDITION SHALL COMPLY WITH THE LATERAL LOAD PROVISIONS
 OF THE FLORIDA BUILDING CODE, BUILDING . ANY AFFECTED
 STRUCTURAL ELEMENTS OF THE EXISTING STRUCTURE MUST ALSO
 DEMONSTRATE THE ABILITY TO COMPLY WITH THE WIND LOAD
 REQUIREMENTS.
  
 1B) THERE WERE NO PRODUCT APPROVALS SUBMITTED FOR THE
 ANDERSON WINDOWS AND DOOR NOR WERE THERE ANY PLANS
 INDICATING THE TYPE OF FASTENERS TO BE USED IN
 ANCHORING THE WINDOWS AND DOORS NOR THE SPACING OF
 ANCHORS.
 RESPONSE INDICATES TO INSTALL STORM PANELS OVER EGRESS
 DOORS, EGRESS DOORS CAN NOT BE BLOCKED BY STORM PANELS.
 GLAZING IN EGRESS DOORS NEED TO MEET TTHE REQUIREMENTS
 FOR LARGE MISSILE IMPACT RESISTANT GLAZING. FBC-B 1609.
 COMPONENTS & CLADDING, FL ADMINISTRATIVE RULE
 9N-3(31)(A).
  
 1C) THE PLANS ALSO INDICATE THERE TO BE STORM SHUTTERS
 TO BE USED FOR COMPLIANCE WITH THE REQUIREMENT FOR
 LARGE MISSILE IMPACT COMPLIANCE, PLEASE PROVIDE
 DOCUMENTATION THAT THE STORM SHUTTERS WILL MEET THE
 REQUIREMENT FOR LARGE MISSILE AND WIND, 2007/09 FBC-B
 1609 COMPONENTS AND CLADDING.
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
 2) COMPLIED.
  
 3) SHEET A2.3 INDICATES THE ROOFING PRODUCT APPROVAL #
 08-0226.06 POLYGLASS SYSTEM, ONCE THE CONTRACTOR IS
 AWARDED THE CONTRACT, THE CONTRACTOR WILL NEED TO
 IDENTIFY WHICH SUB-SYSTEM TO BE INSTALLED, PLEASE NOTE
 SOME OF THE SUB-SYSTEMS MAY REQUIRE INHANCED FASTENING
 IN ZONES 2 & 3.
 RESPONSE NOTED. THIS WILL APEAR AS A BUILDING PROVISO,
 ONCE ALL OTHER CODE ISSUES HAVE BEEN RESOLVED. AT THAT
 TIME THE PROVISO WILL REQUIRE A REVISION FOR THE
 ROOFING SUB-SYSTEM INDENIFICATION AND ENHANCED
 FASTENING SCHEDULE FOR ZONES 2 & 3 ARE PROVIDED. PAGE
 20/20 IF LIMITATION #7 APPLIES CALCULATIONS ARE TO BE
 COMPLETED BY EITHER A FL PE OR ARCHITECT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676