2012-03-14 10:32:49BUILDING PLAN REVIEW
 PERMIT: 11120195
 ADD: 8264 NORTHLAKE BLVD
 CONT: TO BE DETERMINED
 TEL: (561)805-6700 SAM DORFMAN
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 A REPRESENTATIVE NEEDS TO COME IN AND COLLATE THE PLANS
 INTO TWO SETS WITH THE NEW SHEETS INSERTED AND THE OLD
 SHHEETS PULLED OUT BEFORE THE REVIEW CAN TAKE PLACE.
  
  
  
  
 1A) SHEET D1.0 NOTES D1-3 INDICATE THE REUSE OF
 ANDERSON WOOD WINDOWS AND DOORS. THIS BUILDING (PERMIT
 # 94013940) WAS BUILT UNDER THE 1991 SBCCI AND THE WIND
 SPEED WAS 110 MPH FASTEST MILE THAT CONVERTS OVER TO
 130 MPH 3 SECOND GUST UNDERTHE 2007/ 09 FBC-B. HOW WILL
 YOU DEMONSTRATE CODE COMPLIANCE FOR WIND FOR THE
 ANDERSON WINDOWS AND DOORS? 2007/09 FBC-B 1609
 COMPONENTS & CLADDING FOR WIND PRESSURES?
  
 1B) THERE WERE NO PRODUCT APPROVAALS SUBMITTED FOR THE
 ANDERSON WINDOWS AND DOOR NOR WERE THERE ANY PLANS
 INDICATING THE TYPE OF FASTENERS TO BE USED IN
 ANCHORING THE WINDOWS AND DOORS NOR THE SPACING OF
 ANCHORS.
  
 1C) THE PLANS ALSO INDICATE THERE TO BE STORM SHUTTERS
 TO BE USED FOR COMPLIANCE WITH THE REQUIREMENT FOR
 LARGE MISSILE IMPACT COMPLIANCE, PLEASE PROVIDE
 DOCUMENTATION THAT THE STORM SHUTTERS WILL MEET THE
 REQUIREMENT FOR LARGE MISSILE AND WIND, 2007/09 FBC-B
 1609 COMPONENTS AND CLADDING.
  
 2) THE PLANS DO NOT PROVIDE ANY FASTENING OF FRAMING,
 SIDING, DECKING, OR ROOF SHEATHING, THE FASTENING
 TABLES FOUND IN FBC TABLE 2304.9.1 ARE FOR WIND ZONES
 WITH LESS THAN 100 MPH WINDS. 2007/09 FBC-B 2308.2 (4).
  
 3) SHEET A2.3 INDICATES THE ROOFING PRODUCT APPROVAL #
 08-0226.06 POLYGLASS SYSTEM, ONCE THE CONTRACTOR IS
 AWARDED THE CONTRACT, THE CONTRACTOR WILL NEED TO
 IDENTIFY WHICH SUB-SYSTEM TO BE INSTALLED, PLEASE NOTE
 SOME OF THE SUB-SYSTEMS MAY REQUIRE INHANCED FASTENING
 IN ZONES 2 & 3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  