Plan Review Notes
Plan Review Notes For Permit 11120166
Permit Number 11120166
Review Stop E
Sequence Number 1
Notes
Date Text
2011-12-08 17:15:49PROVIDE AN ELECTRICAL WIRING LAYOUT SHOWING THE NEW
 ELECTRICAL OUTLETS PROVIDED. SPECIFICALLY THE PLAN DOES
 NOT INCLUDE THE ELECTRICAL OUTLETS SERVING THE BAR.
 RECEPTACLES WITHIN 6 FEET OF ALL SINKS MUST BE
 PROTECTED BY GFCI'S. NEC 215.5, 210.8
  
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING 711.1
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved