Plan Review Notes
Plan Review Notes For Permit 11120157
Permit Number 11120157
Review Stop B
Sequence Number 1
Notes
Date Text
2011-12-09 16:25:20NOTE: THIS ALTERATION DOES NOT MEET THE 50% RULE FOUND
 IN THE 2007/09 FL. EXISTING BUILDING CODE SECTION
 703.2.2 SUPPLEMENTAL SHAFT
 AND FLOOR OPENING ENCLOSURE REQUIREMENTS, (ELEVATOR
 LOBBIES). WHEN LESS THAN 50% OF THE FLOOR PLATE IS
 BEING REMODELED THEN THE
 ELEVATOR LOBBY AND EXCEPTIONS WILL NOT BE ENFORCED.
 2007/09 FL B C- 707.14 ELEVATOR LOBBIES
  
 BUILDING PROVISO:
 THE FILE ROOM # 1609 IS LARGER THAN 100'-0" SQ FT.
 PLEASE REVIEW FBC-B 508.2.2.1 CONSTRUCTION FOR WALLS,
 FOR INCIDENTAL USE AREAS.
 THE INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF
 RESISTING THE PASSAGE OF SMOKE.
 THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE
 UNDERSIDE OF THE FIRE-RESISTANCE-RATED FLOOR/CEILING
 ASSEMBLY OR FIRE-RESISTANCE-RATED ROOF/
 CEILING ASSEMBLY ABOVE OR TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, OR SUB DECK ABOVE. DOORS SHALL BE
 SELF- OR AUTOMATIC CLOSING
 UPON DETECTION OF SMOKE IN ACCORDANCE WITH SECTION
 715.4.7.3. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS
 AND SHALL NOT BE UNDERCUT
 IN EXCESS OF THE CLEARANCE PERMITTED IN ACCORDANCE WITH
 NFPA 80.