Plan Review Notes For Permit 11120126 |
Permit Number |
11120126 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-23 18:11:20 | PLAN IS ACCEPTABLE WITH PROVISOS: | | | | #1 SHEET E1 IDENTIFIES FPL WORK IN PROXIMITY TO ROW. | | AREA WHERE CONDUITS RUN ALONG FLAGLER | | HAS WATER SERVICES SERVING PARK. ATLEAST TWO CONFLICTS | | WILL BE ENCOUNTERED. | | CALL 811 BEFORE DIGGING AS THIS PLAN DOES NOT NOTE TO | | CALL 811 LOCATES. | | | | #2 CONTRACTOR SHALL OBTAIN ROW PERMIT WITH CITY OF WPB | | SO THAT ROW IN THE VICINITY OF | | THE CONDUIT BE SUPERVISED AS TO ROW ELEMENTS. | | | | #3 SHEET E-15 IDENTIFIES FPL WORK IN PROXIMITY TO ROW. | | CONTRACTOR SHALL OBTAIN ROW PERMIT WITH CITY OF WPB SO | | THAT ROW IN THE VICINITY OF | | THE CONDUIT BE SUPERVISED AS TO ROW ELEMENTS. | | | | MANUEL JULIAN GONZALEZ | | DSD ENGINEERING REVIEW | | 401 CLEMATIS STREET, | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | | | | | |
|