Plan Review Notes For Permit 11120106 |
Permit Number |
11120106 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-28 14:48:56 | 1120106 | | 3601 N. AUSTRALIAN AVE | | LIFT STATION MODIFICATIONS | | | | VERIFY THAT ALL EQUIPMENT INCLUDING THE GENERATOR HAS | | BEEN ELEVATED ABOVE THE ESTABLISHED FLOOD ELEVATION. | | FBC BUILDING 3110.1.2 | | VERIFY ALL FIXTURES ARE APPROVED FOR THE LOCATION. | | SHEET E5 IS MISSING FROM THE PLAN SUBMITTED. NEC 410.10 | | PROVIDE A SAFETY LABELING PLAN FOR ELECTRICAL EQUIPMENT | | ROOM. NEC 110.22, 110.16 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|