 3601 N. AUSTRALIAN AVE
 LIFT STATION MODIFICATIONS
  
 VERIFY THAT ALL EQUIPMENT INCLUDING THE GENERATOR HAS
 BEEN ELEVATED ABOVE THE ESTABLISHED FLOOD ELEVATION.
 FBC BUILDING 3110.1.2
 VERIFY ALL FIXTURES ARE APPROVED FOR THE LOCATION.
 SHEET E5 IS MISSING FROM THE PLAN SUBMITTED. NEC 410.10
 PROVIDE A SAFETY LABELING PLAN FOR ELECTRICAL EQUIPMENT
 ROOM. NEC 110.22, 110.16
  