Plan Review Notes
Plan Review Notes For Permit 11120106
Permit Number 11120106
Review Stop B
Sequence Number 1
Notes
Date Text
2011-12-20 16:32:13BUILDING PLAN REVIEW
 PERMIT: 11120106
 ADD: 3601 N AUSTRALIAN AVE.
 CONT: TO BE DETERMINED
 SUZANNE HALVERSON
 TEL: (561)494-1075
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE SURVEY & PCN ARE FOR 1815 DOCK STREET NOT THE
 ADDRESS PROPOSED ON THE PERMIT APPLICATION, PLEASE
 CORRECT.
  
 2) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 3) PLEASE NOTE THIS PROJECT IS LOCATED IN A FLOOD ZONE.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A-9" FLOOD
 ZONE FINISH FLOOR ELEVATION SHALL BE 13.5' NGVD OR,
 TOGETHER WITH ATTENDANT UTILITY AND SANITARY
 FACILITIES, BE FLOODPROOFED SO THAT BELOW SIX INCHES
 ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS WATERTIGHT,
 WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE PASSAGE OF
 WATER AND WITH STRUCTURAL COMPONENTS HAVING THE
 CAPABILITY OF RESISTING HYDROSTATIC AND HYDRODYNAMIC
 LOADS AND EFFECTS OF BUOYANCY. A REGISTERED
 PROFESSIONAL ENGINEER OR ARCHITECT SHALL CERTIFY THAT
 THE STANDARDS OF THIS SUBSECTION ARE SATISFIED. SUCH
 CERTIFICATION SHALL BE PROVIDED TO THE CITY ENGINEER. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 94-546(B)(2)(2) NONRESIDENTIAL CONSTRUCTION. ALL NEW
 CONSTRUCTION OR SUBSTANTIAL IMPROVEMENT OF ANY
 COMMERCIAL, INDUSTRIAL OR OTHER NONRESIDENTIAL
 STRUCTURE SHALL EITHER HAVE THE LOWEST FLOOR, INCLUDING
 BASEMENT, ELEVATED TO THE LEVEL OF SIX INCHES ABOVE THE
 BASE FLOOD ELEVATION OR, TOGETHER WITH ATTENDANT
 UTILITY AND SANITARY FACILITIES, BE FLOODPROOFED SO
 THAT BELOW SIX INCHES ABOVE THE FLOOD BASE LEVEL THE
 STRUCTURE IS WATERTIGHT, WITH WALLS SUBSTANTIALLY
 IMPERMEABLE TO THE PASSAGE OF WATER AND WITH STRUCTURAL
 COMPONENTS HAVING THE CAPABILITY OF RESISTING
 HYDROSTATIC AND HYDRODYNAMIC LOADS AND EFFECTS OF
 BUOYANCY. A REGISTERED PROFESSIONAL ENGINEER OR
 ARCHITECT SHALL CERTIFY THAT THE STANDARDS OF THIS
 SUBSECTION ARE SATISFIED. SUCH CERTIFICATION SHALL BE
 PROVIDED TO THE CITY ENGINEER
  
 94-611 SUBSTANTIAL IMPROVEMENT MEANS ANY COMBINATION OF
 REPAIRS, RECONSTRUCTION, ALTERATION, OR IMPROVEMENTS TO
 A STRUCTURE, TAKING PLACE DURING THE LIFE OF A
 STRUCTURE, IN WHICH THE CUMULATIVE COST EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE
 STRUCTURE. THE MARKET VALUE OF THE STRUCTURE SHOULD BE
 THE APPRAISED VALUE OF THE STRUCTURE PRIOR TO THE START
 OF THE INITIAL REPAIR OR IMPROVEMENT, OR IN THE CASE OF
 DAMAGE, THE VALUE OF THE STRUCTURE PRIOR TO THE DAMAGE
 OCCURRING. FOR THE
 7)
 PURPOSES OF THIS DEFINITION, "SUBSTANTIAL IMPROVEMENT"
 IS CONSIDERED TO OCCUR WHEN THE FIRST ALTERATION OF ANY
 WALL, CEILING, FLOOR, OR OTHER STRUCTURAL PART OF THE
 BUILDING COMMENCES, WHETHER OR NOT THAT ALTERATION
 AFFECTS THE EXTERNAL DIMENSIONS OF THE STRUCTURE. THE
 TERM "SUBSTANTIAL IMPROVEMENT" DOES NOT, HOWEVER,
 INCLUDE ANY IMPROVEMENT OF A STRUCTURE TO COMPLY WITH
 EXISTING HEALTH, SANITARY, OR SAFETY CODES WHICH ARE
 SOLELY NECESSARY TO ENSURE SAFE LIVING CONDITIONS.
  
 PLEASE REVIEW SHEET C-1 AND THE FLOOR ELEVATION OF THE
 EXISTING LIFT STATION AND THE LISTED REQUIREMENTS FOR
 SUBSTANTIAL IMPROVEMENT, INDICATE HOW THE STRUCTURE
 WILL COME INTO COMPLIANCE BY EITHER FLOOD PROOFING OR
 CHANGING THE FINISH FLOOR ELEVATION. THIS WILL ALSO BE
 REQUIRED FOR THE GENERATOR PAD FOUND ON SHEET C-2.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) 1808.2.2 PIER AND PILE FOUNDATIONS SHALL BE DESIGNED
 AND INSTALLED ON THE BASIS OF A FOUNDATION
 INVESTIGATION AS DEFINED IN SECTION 1802, UNLESS
 SUFFICIENT DATA UPON WHICH TO BASE THE DESIGN AND
 INSTALLATION IS AVAILABLE.
  
 THE INVESTIGATION AND REPORT PROVISIONS OF SECTION 1802
 SHALL BE EXPANDED TO INCLUDE, BUT NOT BE LIMITED TO,
 THE FOLLOWING:
 4.1. RECOMMENDED PIER OR PILE TYPES AND INSTALLED
 CAPACITIES.
 4.2. RECOMMENDED CENTER-TO-CENTER SPACING OF PIERS OR
 PILES.
 4.3 DRIVING CRITERIA.
 4.4. INSTALLATION PROCEDURES.
 4.5. FIELD INSPECTION AND REPORTING PROCEDURES (TO
 INCLUDE PROCEDURES FOR VERIFICATION OF THE INSTALLED
 BEARING CAPACITY WHERE REQUIRED).
 4.6. PIER OR PILE LOAD TEST REQUIREMENTS.
 4.7. DURABILITY OF PIER OR PILE MATERIALS.
 4.8. DESIGNATION OF BEARING STRATUM OR STRATA.
 4.9. REDUCTIONS FOR GROUP ACTION, WHERE NECESSARY.
  
 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6)FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS AND FANS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 7) SHEET S1 PROVIDES THE WIND DESIGN CRITERIA BUT NOT
 THE PRESSURES FOR ZONES 1,2,3 (ROOF ZONES) NOR (WALL
 ZONES) 4 &5.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  