2011-12-08 14:58:51****CORRECTIONS****
 FAN SPECIFICATION SUBMITTED BY CONTRACTOR VIA FAX
  
 1. AIR REQUIRED BY FBC MECHANICAL 403.3 SHALL NOT BE
 RECIRCULATED, FBC MECHANICAL 403.2.1.
  
 2. THE PERSON TAKING RESPONSIBILITY FOR THE PLAN IS TO
 PROVIDE SIGNATURE AND PRINTED NAME, FS471, FS481,
 FS489.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  
  
  