2011-12-19 13:54:352007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING RISER DIAGRAM THAT WAS SUBMITTED IS NOT
 LEGIBLE. THE APPROVED DRAWINGS WILL BE DIGITALLY COPIED
 FOR PUBLIC RECORD. PLEASE SUBMIT 2 SETS OF CLEAR AND
 LEGIBLE RISER DIAGRAMS. CITY AMENDMENTS 106.1.1
  
 2) PROVIDE TWO SETS OF A RISER DIAGRAM FOR THE GARAGE
 APARTMENT. CITY AMENDMENTS 106.3.5.4
  
 3) THE PLUMBING RISER DIAGRAM IS REQUIRED TO MATCH THE
 ARCHITECTURAL PLANS. CITY AMENDMENTS 106.1.1
  
 4) THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL
 HAVE AT LEAST ONE VENT PIPE THAT EXTENDS TO THE
 OUTDOORS. FBC P3102.1
  