Plan Review Notes
Plan Review Notes For Permit 11120079
Permit Number 11120079
Review Stop M
Sequence Number 1
Notes
Date Text
2011-12-22 11:01:012007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS SPECIFY 27,400 BTU FOR A/C UNIT
 #2 IN THE UPSTAIRS AREA WHICH DOES NOT CORRESPOND WITH
 THE MANUAL J CALCULATIONS THAT REQUIRE 43,862 BTU FOR
 SYSTEM #2. PLEASE CORRECT. FBCR M1401.3
  
 2) THE ENERGY CALCULATIONS APPEAR TO HAVE COMBINED THE
 DETACHED GARAGE APARTMENT WITH THE SINGLE FAMILY
 RESIDENCE. PLEASE PROVIDE SEPARATE ENERGY CALCULATIONS
 FOR EACH BUILDING. FBC N1100.0
  
 3) THE GARAGE APARTMENT IS NEW CONSTRUCT AND THE SINGLE
 FAMILY RESIDENCE IS AN ADDITION TO AN EXISTING
 BUILDING. PLEASE INDICATE THIS ON ENERGY CALC. FORMS.
  
 4) THE ADJACENT FLOOR-CEILING ASSEMBLY SEPARATING THE
 GARAGE FROM THE CONDITIONED SPACE ABOVE IS REQUIRED TO
 BE INSULATED. N1105.AB.1
  
 5) SPECIFY THE WATER HEATER SYSTEM FOR THE GARAGE
 APARTMENT. N1112.AB
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]