Plan Review Notes For Permit 11120079 |
Permit Number |
11120079 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-22 11:01:01 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) THE MECHANICAL PLANS SPECIFY 27,400 BTU FOR A/C UNIT | | #2 IN THE UPSTAIRS AREA WHICH DOES NOT CORRESPOND WITH | | THE MANUAL J CALCULATIONS THAT REQUIRE 43,862 BTU FOR | | SYSTEM #2. PLEASE CORRECT. FBCR M1401.3 | | | | 2) THE ENERGY CALCULATIONS APPEAR TO HAVE COMBINED THE | | DETACHED GARAGE APARTMENT WITH THE SINGLE FAMILY | | RESIDENCE. PLEASE PROVIDE SEPARATE ENERGY CALCULATIONS | | FOR EACH BUILDING. FBC N1100.0 | | | | 3) THE GARAGE APARTMENT IS NEW CONSTRUCT AND THE SINGLE | | FAMILY RESIDENCE IS AN ADDITION TO AN EXISTING | | BUILDING. PLEASE INDICATE THIS ON ENERGY CALC. FORMS. | | | | 4) THE ADJACENT FLOOR-CEILING ASSEMBLY SEPARATING THE | | GARAGE FROM THE CONDITIONED SPACE ABOVE IS REQUIRED TO | | BE INSULATED. N1105.AB.1 | | | | 5) SPECIFY THE WATER HEATER SYSTEM FOR THE GARAGE | | APARTMENT. N1112.AB | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|