2012-01-05 15:08:1411120079
 219 AVILA RD.
 RESIDENTIAL ADDITION
  
 ELECTRICAL RISER PLAN IS NOT CLEARLY LEGIBLE. PLEASE
 RESUBMIT. NEC 215.5
 PANEL BOARD FEEDERS ARE UNDERSIZED. MINIMUM #3/0, AND
 #3 REQUIRED. NEC 310.16
 PLEASE LOCATE THE CARBON MONOXIDE ALARMS ON THE PLANS
 IN ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS.
 PLAN NOTES ARE NOT AN ACCEPTABLE ALTERNATIVE. ADD A
 CARBON MONOXIDE DETECTOR FOR THE 2ND FLOOR BEDROOMS
 INCLUDING THE STUDIO. FBC R313
 IN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 ELECTRIC SERVICE. NEC 250.94
 ADDITIONAL RECEPTACLES ARE REQUIRED IN THE FOYER. NEC
 210.52
 AC DISCONNECTS MAY NOT BE BLOCKED BY THE CONDITIONING
 UNITS. NEC 110.26
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  