Plan Review Notes
Plan Review Notes For Permit 11120079
Permit Number 11120079
Review Stop B
Sequence Number 1
Notes
Date Text
2011-12-22 16:49:022007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) ON SHEET A.02 AND A.03 THERE IS A SECTION MARK FOR
 SECTION 13 ON A.07. THERE IS NO SECTION 13 ON A.07.
 PLEASE CLARIFY. CITY AMENDMENTS 106.1.1
  
 2) ON SHEET A.02 THERE IS A SECTION THROUGH THE
 CONCRETE STAIRS AT THE GARAGE MARKED 13 ON A.07. THERE
 IS NO SECTION 13 ON A.07. PLEASE CLARIFY. CITY
 AMENDMENTS 106.1.1
  
 3) THE WINDER TREADS ON THE INTERIOR STAIRS ARE
 REQUIRED TO COMPLY WITH FBCR 311.5.3.2 WHICH REQUIRES A
 MINIMUM TREAD DEPTH OF 10" AT A POINT 12" FROM THE SIDE
 WHERE THE TREADS ARE NARROWER AND A MINIMUM TREAD DEPTH
 OF 6" AT ANY POINT.
  
 4) PROVIDE A SECTION THROUGH THE GARAGE APARTMENT.
 SPECIFY THE INSULATION IN THE WALLS, CEILING AND FLOOR.
 CITY AMENDMENTS 106.1.1
  
 5) SHOW COMPLIANCE WITH FBC R309.2 FOR SEPARATION
 REQUIREMENTS BETWEEN GARAGE AND LIVING SPACE.
  
 6) SUBMIT ROOF SCUPPER SIZING CALCULATIONS FOR THE
 GARAGE APARTMENT. SPECIFY THE LOCATIONS AND SIZES OF
 THE PRIMARY AND OVERFLOW SCUPPERS. FBC R903.4
  
 7) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES
 GUTTERS WITH DOWNSPOUTS WITH OF LESS THAN 6 INCHES
 HORIZONTAL PROJECTION AND DOWNSPOUTS TO DISCHARGE AT
 LEAST ONE FOOT AWAY FROM THE STRUCTURE SIDE WALL.
  
 8) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOW
 AND DOOR OPENINGS ON SHEETS A.02 AN A.03 OF THE
 ARCHITECTURAL PLANS DO NOT CORRESPOND WITH THE
 STRUCTURAL PLANS. THE PRESSURES ON THE ARCHITECTURAL
 PLANS ARE BASED ON EXPOSURE CATEGORY B AND THE
 STRUCTURAL PLANS ARE BASED ON EXPOSURE C. PLEASE
 CORRECT. FBC R301.2.1
  
 9) SOME OF THE PRODUCT APPROVALS SPECIFIED ON SHEET
 A.01 DO NOT CORRESPOND WITH THE PRODUCT APPROVALS THAT
 WERE SUBMITTED. PLEASE CORRECT. CITY AMENDMENTS 106.1.1
  
 10) THE DESIGN PRESSURES LISTED IN THE PRODUCT
 APPROVALS FOR SOME OF THE DOORS DO NOT MEET THE
 COMPONENT AND CLADDING PRESSURES FOR EXPOSURE C IN WALL
 ZONE 5. FBC R301.2.1 PLEASE REVIEW.
  
 11) THE DOOR AT THE SIDE LOGGIA IS LABELED 2 ON A.02,
 WHICH IS THE OVER HEAD GARAGE DOOR. PLEASE CLARIFY.
 CITY AMENDMENTS 106.1.1
  
 12) SUBMIT TWO SETS OF EVALUATION REPORTS FOR THE SPRAY
 FOAM INSULATION TO SHOW COMPLIANCE WITH FBC R314.
  
 13) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DOUBLE
 FIXED LITE DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 CASEMENT WINDOWS AS REQUIRED BY DCA RULE 9N-3. THE ONES
 THAT WERE SUBMITTED ARE FOR PROJECTED WINDOWS (AWNING).
  
 15) SPECIFY THE APPROVED ASSEMBLY AND FASTENING OPTION
 FROM THE PRODUCT APPROVAL THAT WILL BE USED TO INSTALL
 THE GAF MODIFIED ROOF SYSTEM. SUBMIT TWO SIGNED AND
 SEALED SETS OF RAS 117 CALCULATIONS FOR THE ENHANCED
 FASTENING OF THE BASE SHEET IN ORDER TO MEET THE HIGHER
 UPLIFT PRESSURES AT THE PERIMETER AND CORNER ROOF
 AREAS. FBC R905.12.3
  
 16) SPECIFY THE ATTACHMENT METHOD AND ATTACHMENT
 RESISTANCE MOMENT FROM THE CONCRETE ROOF TILE PRODUCT
 APPROVAL THAT WILL BE USED TO INSTALL THE TILE.FBC
 R905.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]