2011-12-22 16:49:02 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) ON SHEET A.02 AND A.03 THERE IS A SECTION MARK FOR |
| SECTION 13 ON A.07. THERE IS NO SECTION 13 ON A.07. |
| PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 |
| |
| 2) ON SHEET A.02 THERE IS A SECTION THROUGH THE |
| CONCRETE STAIRS AT THE GARAGE MARKED 13 ON A.07. THERE |
| IS NO SECTION 13 ON A.07. PLEASE CLARIFY. CITY |
| AMENDMENTS 106.1.1 |
| |
| 3) THE WINDER TREADS ON THE INTERIOR STAIRS ARE |
| REQUIRED TO COMPLY WITH FBCR 311.5.3.2 WHICH REQUIRES A |
| MINIMUM TREAD DEPTH OF 10" AT A POINT 12" FROM THE SIDE |
| WHERE THE TREADS ARE NARROWER AND A MINIMUM TREAD DEPTH |
| OF 6" AT ANY POINT. |
| |
| 4) PROVIDE A SECTION THROUGH THE GARAGE APARTMENT. |
| SPECIFY THE INSULATION IN THE WALLS, CEILING AND FLOOR. |
| CITY AMENDMENTS 106.1.1 |
| |
| 5) SHOW COMPLIANCE WITH FBC R309.2 FOR SEPARATION |
| REQUIREMENTS BETWEEN GARAGE AND LIVING SPACE. |
| |
| 6) SUBMIT ROOF SCUPPER SIZING CALCULATIONS FOR THE |
| GARAGE APARTMENT. SPECIFY THE LOCATIONS AND SIZES OF |
| THE PRIMARY AND OVERFLOW SCUPPERS. FBC R903.4 |
| |
| 7) SHOW COMPLIANCE WITH FBC R320.7 WHICH REQUIRES |
| GUTTERS WITH DOWNSPOUTS WITH OF LESS THAN 6 INCHES |
| HORIZONTAL PROJECTION AND DOWNSPOUTS TO DISCHARGE AT |
| LEAST ONE FOOT AWAY FROM THE STRUCTURE SIDE WALL. |
| |
| 8) THE COMPONENT AND CLADDING PRESSURES FOR THE WINDOW |
| AND DOOR OPENINGS ON SHEETS A.02 AN A.03 OF THE |
| ARCHITECTURAL PLANS DO NOT CORRESPOND WITH THE |
| STRUCTURAL PLANS. THE PRESSURES ON THE ARCHITECTURAL |
| PLANS ARE BASED ON EXPOSURE CATEGORY B AND THE |
| STRUCTURAL PLANS ARE BASED ON EXPOSURE C. PLEASE |
| CORRECT. FBC R301.2.1 |
| |
| 9) SOME OF THE PRODUCT APPROVALS SPECIFIED ON SHEET |
| A.01 DO NOT CORRESPOND WITH THE PRODUCT APPROVALS THAT |
| WERE SUBMITTED. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| |
| 10) THE DESIGN PRESSURES LISTED IN THE PRODUCT |
| APPROVALS FOR SOME OF THE DOORS DO NOT MEET THE |
| COMPONENT AND CLADDING PRESSURES FOR EXPOSURE C IN WALL |
| ZONE 5. FBC R301.2.1 PLEASE REVIEW. |
| |
| 11) THE DOOR AT THE SIDE LOGGIA IS LABELED 2 ON A.02, |
| WHICH IS THE OVER HEAD GARAGE DOOR. PLEASE CLARIFY. |
| CITY AMENDMENTS 106.1.1 |
| |
| 12) SUBMIT TWO SETS OF EVALUATION REPORTS FOR THE SPRAY |
| FOAM INSULATION TO SHOW COMPLIANCE WITH FBC R314. |
| |
| 13) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DOUBLE |
| FIXED LITE DOORS AS REQUIRED BY DCA RULE 9N-3. |
| |
| 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| CASEMENT WINDOWS AS REQUIRED BY DCA RULE 9N-3. THE ONES |
| THAT WERE SUBMITTED ARE FOR PROJECTED WINDOWS (AWNING). |
| |
| 15) SPECIFY THE APPROVED ASSEMBLY AND FASTENING OPTION |
| FROM THE PRODUCT APPROVAL THAT WILL BE USED TO INSTALL |
| THE GAF MODIFIED ROOF SYSTEM. SUBMIT TWO SIGNED AND |
| SEALED SETS OF RAS 117 CALCULATIONS FOR THE ENHANCED |
| FASTENING OF THE BASE SHEET IN ORDER TO MEET THE HIGHER |
| UPLIFT PRESSURES AT THE PERIMETER AND CORNER ROOF |
| AREAS. FBC R905.12.3 |
| |
| 16) SPECIFY THE ATTACHMENT METHOD AND ATTACHMENT |
| RESISTANCE MOMENT FROM THE CONCRETE ROOF TILE PRODUCT |
| APPROVAL THAT WILL BE USED TO INSTALL THE TILE.FBC |
| R905.3 |
| |