Plan Review Notes For Permit 11120076 |
Permit Number |
11120076 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-05 11:40:55 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PLEASE PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER | | AREAS TO MEET THE DESIGN PRESSURES REQUIRED BY SEC. | | R301.2.1.4.3. GENERAL LIMITATION #7 ON NOA 09-0224.01 | | SUBMITTED REQUIRES CALCULATIONS TO BE SIGNED AND | | SEALED. ***NOTE: DESIGN PROFESSIONAL DOING THE | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS | | BUILDING IS LOCATED ON EXPOSURE "C". SEE SEC. | | R301.2.1.4.3. | | | | 2- PLEASE CLARIFY IF DOING AN INSULATED ROOF AND A | | NON-INSULATED ROOF. PROVIDE RAS 117 CALCULATIONS FOR | | EACH ONE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|