2013-07-09 15:51:30 | BUILDING PLAN REVIEW |
| PERMIT:11120073 |
| ADD: 700 N CONGRESS |
| CONT: TO BE DETERMINED |
| CONTACT: VIVEK GALAV |
| TEL: (561)644-7416 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| |
| ARCHITECT: REG RICK GONZALEZTEL: 659-2383 |
| STRUCTURAL ENGINEER: ANDREW MORGAN P. E. |
| TEL: 881-8999 |
| BUILDING PLAN REVIEW |
| PERMIT:11120073 |
| ADD: 700 N CONGRESS |
| CONT: TO BE DETERMINED |
| CONTACT: JEFF HALVERSONTEL: (561)644-7416 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| |
| ARCHITECT: REG RICK GONZALEZ |
| TEL: 659-2383 |
| STRUCTURAL ENGINEER: ANDREW MORGAN P. E. |
| TEL: 881-8999 |
| |
| 5TH REVIEW |
| DATE: JULY 09/ 2013 |
| ACTION: PROVISO |
| |
| BUILDING PROVISO: |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL |
| RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF |
| RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL |
| REVIEWS WITH ASSOCIATED FEES. |
| |
| 1) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING& FAC |
| RULE 9N-3, PLEASE PROVIDE 2 COPIES OF PRODUCT TESTING |
| REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| 1A) FIXED GLAZING, STOREFRONT |
| 1B) OPERABLE GLAZING UNITS |
| 1C) MULLIONS, HORIZONTAL AND VERTICAL |
| 1D) GLASS BLOCK |
| 1E) EXTERIOR GLAZED SWING DOORS |
| 1F) EXTERIOR INSULATED METAL SWING DOORS |
| 1G) BI-FOLD APPARATUS BAY DOORS/ WITH TRANSOM |
| 1H) EXTERIOR ROOF WALL ACCESS DOOR/ FRAME (H) |
| 1I) DOUBLE ACCESS PANEL ROOF HATCH, INSULATED -182.6. |
| 1J) WALL LOUVERS |
| 1K) A/C ROOF TOP A/C STANDS |
| 1L) ROOF ASSEMBLIES FLAT ROOF INCLUSIVE OF ROOF TOP |
| INSULATION. |
| 1M) ROOF ASSEMBLIES SLOPED ROOF, METAL ROOF SYSTEMS |
| -266.9 ZONE 3 AND -372.5 ROOF OVERHANGS WITHIN ZONE# 3. |
| 1N) BAHAMA SHUTTERS WITH PRODUCT APPROVAL FOR CLOSED |
| POSITION AND ENGINEERING ANALYSIS FOR SHUTTERS WHEN |
| LEFT IN THE OPEN POSITION IN THE CASE OF A HIGH WIND |
| EVENT. |
| 1O) ROOFTOP EXHAUST FANS |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) REVISION IS REQUIRED FOR THE ELIMINATION OF STONE |
| VENEER ON EXTERIOR WALL OR COMPLIANCE WITH: |
| 2010 FBC-B 2114.2 CONCRETE BEARING LEDGE. |
| BRICK, STONE OR OTHER VENEER SHALL BE SUPPORTED BY A |
| CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL |
| THICKNESS OF THE BRICK, STONE OR OTHER VENEER, WHICH IS |
| POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO |
| SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL |
| CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT |
| SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE |
| IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL |
| BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL |
| SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED |
| IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW |
| GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED |
| TO THE CAVITY CREATED BETWEEN THE VENEER AND THE |
| FOUNDATION, IN LIEU OF A PHYSICAL BARRIER. |
| EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL |
| SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH |
| TMS 402/ACI 530/ASCE 5, PROVIDED AT LEAST A 6-INCH (152 |
| MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL |
| EXTERIOR EXISTS BETWEEN THE VENEER AND THE TOP OF ANY |
| SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING |
| COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK |
| IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE. |
| JIM, |
| WE WILL REMOVE THE STONE VENEER FROM FIRE STATION 5 AND |
| REPLACE IT WITH STUCCO. |
| THANKS. |
| VIVEK |
| ----- FORWARDED BY VIVEK GALAV/WESTPALM ON 06/18/2013 |
| 02:47 PM ----- |
| FROM: VINCENT KAFER |
| TO: "[email protected]" |
| DATE: 06/18/2013 11:07 AM |
| SUBJECT: FS#5-EOC PERMITTING |
| CAN YOU PLEASE PROVIDE A LETTER TO JIM WIETMER |
| (BUILDING DEPARTMENT) STATING THAT THE CITY HAS DECIDED |
| REMOVING THE STONE VENEER AND REPLACING IT PER STUCCO? |
| THANKS |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |