2013-06-24 13:33:43 | 11120073 |
| 700 N. CONGRESS |
| NEW FIRE STATION |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| SHEET E-0.01 |
| INDICATE THE CLASSIFICATIONS OF THE FACILITY UNDER THE |
| 2008 NATIONAL ELECTRIC CODE REQUIREMENTS FOR CRITICAL |
| OPERATIONS POWER SYSTEMS (COPS). NEC ARTICLE 708 |
| |
| SHEET E-0.03 |
| ELECTRICAL CIRCUITS AND LIGHTING POLES HAVE NOT BEEN |
| SPECIFIED FOR THE SITE LIGHTING. PROVIDE SIGNED AND |
| SEALED WIND LOADING CERTIFICATION FOR THE LIGHT POLE |
| ASSEMBLY WITH FIXTURES. THIS MAY BE ACCOMPLISHED UNDER |
| A SEPERATE PERMIT. 2010 FBC 1609.1., ASCE 7-10 |
| |
| SHEET E-0.04 |
| VERIFY THE GENERATOR SERVICE DISCONNECT IS SERVICE |
| RATED AND IS GROUNDED FAULT PROTECTED (GFP) OR HAS A |
| GFP INDICATOR. SEE NEC 701.17 |
| |
| THE SECONDARY OC PROTECTION ON T-L1 APPEARS TO EXCEED |
| THE MAXIMUM ALLOWABLE RATING. NEC 450.3(B) |
| |
| SHEET E-1.01 |
| ELECTRICAL CIRCUITS SERVING THE LIVING AND SLEEPING |
| AREAS REQUIRE AFCI PROTECTION. NEC 210.12, 210.18 |
| |
| IDENTIFY THE MINIMUM WIRING METHOD PROPOSED IN ALL |
| CLASS 1 DIVISION 2 AREAS. NEC 501.10(B), 501.15(B) |
| |
| SHEET E-4.01 |
| THE ELECTRICAL PLAN IS UNCLEAR AS TO THE CLASSIFICATION |
| OF THE IT ROOMS UNDER THE ELECTRIC CODE. NEC 645.4 |
| |
| THE PLANS ARE UNCLEAR AS TO HOW THE IT ROOMS ARE TO BE |
| VENTILATED. NEC 645.4, 480.9 |
| |
| PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE |
| REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL |
| ROOMS. NEC 110.22, 110.16, 701.9 |
| |
| NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE LIGHTNING |
| PROTECTION SYSTEM, SITE LIGHTING, AUDIO, SECURITY, SITE |
| TRAILERS, GATES, DATA AND PHONES. |
| |
| |
| ROBERT LECKY |
| ELECTRIC PLANS EXAMINER |